64
enabled the evaporator fan is
turned off (maximum for the time
i3 or when the input is disabled)
(8)
1 = INPUT MICROPORT – in
this case parameters i1, i2 and i3
are active; when the input is
enabled the compressor is shut-
down and the evaporator fan is
turned off (maximum for the time
i3 or when the input is disabled)
(8) (9)
2
=
COMPRESSOR
PROTECTION – in this case
parameters i1 and i7 are active; the
compressor is shut-down, code
“iA” flashes on the display and the
buzzer is activated (until the input
is disabled)
i1
0
2
---
2
type of contact for the digital input
0 = NO (input enabled with
contact closed)
1 = NO (input enabled with
contact opened)
2 = no input
i2
-1
120
min
30
delay in prompt for alarm input
microport (only if i0 = 0 or 1)
-1 = no alarm prompt
i3
-1
120
min
15
maximum duration caused when
the input microport is enabled
(only if i0 = 0 or 1)
-1 = the resulting condition
remains until input is disabled
i7
0
120
min
0
delay in compressor from when
the input compressor protection is
disabled (only if i0 = 2)