Introduction & Company Profile
3
Guarantee
4
Nemtek Group Outlets
5
Symbol Key
6
Energizer Details & Mounting
7
Energizer Features
8
Product Specifications
9
Operating the Energizer
10
Using the Nemtek Tag
10
Installation Notes
12
Appendix
13 - 16
Document Revision History
17
AGRI Solar
Table of Contents
2
General requirements for electric fences
Electric fences shall be installed and operated so that they cause no electrical hazard to persons, animals or
their surroundings.
Electric fence constructions which are likely to lead to the entanglement of animals or persons shall be
avoided.
An electric fence shall not be supplied from two different energizers or from independent fence circuits of the
same energizer.
For any two different electric fences, each supplied from a different energizer with independent timing, the
distance between the wires of the two electric fences shall be at least 2.5m. If this gap is to be closed, this
shall be affected by means of electrically nonconductive material or an isolated metal barrier.
Barbed wire or razor wire shall not be electrified by an energizer.
Electric fences and their ancillary equipment shall be installed, operated and maintained in a manner that
minimizes danger to persons, and reduces the risk of persons receiving an electric shock unless they attempt
to penetrate the physical barrier, or are in a secure area without authority. Exposed conductive parts of the
physical barrier shall be effectively earthed.
A spacing of 2.5m shall be maintained between non insulated electric fence conductors or non insulated
connecting leads supplied from different energizers. This spacing may be less where conductors or
connecting leads are covered by insulating sleeving, or consist of insulated cables, rated to at least 10kV.
This requirement need not apply where the separately energized conductors are separated by a physical
barrier, which does not have any openings greater than 50mm.
A vertical separation of not less than 2m shall be maintained between pulsed conductors fed from different
energizers.
Ensure that all ancillary equipment connected to the electric fence circuit provides a degree of isolation
between the fence circuit and the supply mains equivalent to that provided by the energizer. Protection from
the weather shall be provided to the ancillary equipment unless this equipment is certified by the
manufacturer as being suitable for use outdoors, and is of a type with a minimum degree of protection IPx4.
Connecting leads that are run inside buildings shall be effectively insulated from the earthed structural parts
of the building. This may be achieved by using insulated high voltage cable.
Connecting leads that are run underground shall be run in a conduit of insulating material or else insulated
high voltage cable shall be used. Care shall be taken to avoid damage to the connecting leads due to
external factors.
Connecting leads shall not be installed in the same conduit as the mains supply wiring, communication cables
or data cables.
AGRI Solar
Appendix
14
General requirements for electric fences
Electric fences shall be installed and operated so that they cause no electrical hazard to persons, animals or
their surroundings.
Electric fence constructions which are likely to lead to the entanglement of animals or persons shall be
avoided.
An electric fence shall not be supplied from two different energizers or from independent fence circuits of the
same energizer.
For any two different electric fences, each supplied from a different energizer with independent timing, the
distance between the wires of the two electric fences shall be at least 2.5m. If this gap is to be closed, this
shall be affected by means of electrically nonconductive material or an isolated metal barrier.
Barbed wire or razor wire shall not be electrified by an energizer.
Electric fences and their ancillary equipment shall be installed, operated and maintained in a manner that
minimizes danger to persons, and reduces the risk of persons receiving an electric shock unless they attempt
to penetrate the physical barrier, or are in a secure area without authority. Exposed conductive parts of the
physical barrier shall be effectively earthed.
A spacing of 2.5m shall be maintained between non insulated electric fence conductors or non insulated
connecting leads supplied from different energizers. This spacing may be less where conductors or
connecting leads are covered by insulating sleeving, or consist of insulated cables, rated to at least 10kV.
This requirement need not apply where the separately energized conductors are separated by a physical
barrier, which does not have any openings greater than 50mm.
A vertical separation of not less than 2m shall be maintained between pulsed conductors fed from different
energizers.
Ensure that all ancillary equipment connected to the electric fence circuit provides a degree of isolation
between the fence circuit and the supply mains equivalent to that provided by the energizer. Protection from
the weather shall be provided to the ancillary equipment unless this equipment is certified by the
manufacturer as being suitable for use outdoors, and is of a type with a minimum degree of protection IPx4.
Connecting leads that are run inside buildings shall be effectively insulated from the earthed structural parts
of the building. This may be achieved by using insulated high voltage cable.
Connecting leads that are run underground shall be run in a conduit of insulating material or else insulated
high voltage cable shall be used. Care shall be taken to avoid damage to the connecting leads due to
external factors.
Connecting leads shall not be installed in the same conduit as the mains supply wiring, communication cables
or data cables.
AGRI Solar
Appendix
14