41
3.3.7.4.3. Push Button
Push buttons can be attached to the ePowerSwitch 8M+
R2
to trigger manually pre-programmed
actions.
You can connect a Push Button to the RJ45 A-xBus connector on the ePowerSwitch
*
8M+
R2
or behind an
xBus peripheral already connected to the ePowerSwitch 8M+
R2
(Daisy Chain Connection).
To connect a Push button to the ePowerSwitch 8M+
R2
, use following procedure:
1. Set the dip switches of the Push button so that the selected I/O address does not conflict with another
Push button or another Digital Input Module already installed (see user's guide of the Push button).
- Do NOT connect the xBus cable before setting its DIP switches.
- Do NOT use the same address for two different Push buttons.
2. Using a standard RJ45 network cable, connect the Push button to the RJ45 xBus connector on the
ePowerSwitch 8M+
R2
or behind another xBus peripheral already connected to the ePowerSwitch
8M+
R2
.
To configure the Push button, use following Log in procedure:
1. Open you browser and log in to the Administrator's Configuration Page,
(ex.
http://192.168.100.200/sysadmin.htm
).
2. Enter the administrator name and password (default for both = admin). The home page appears.
3. Click on the Settings and then on the Peripherals Tab.
If the Push button is properly connected to the ePowerSwitch 8M+
R2
it will be automatically recognized
and displayed on this page after a delay of 1 to 60 seconds. In this case, the colour of the corresponding
Edit and Info symbol is red.
The Peripheral page is not automatically refreshed, so you need to refresh it by clicking the
peripheral TAB again (or push [F5] or press <CTRL-R> on your keyboard if you use Internet
Explorer or Mozilla Firefox).
Problem / Troubleshooting
y
If you choose any setting that is already in use by another
Push button or another Digital Input Module
connected to the ePowerSwitch 8M+
R2
, a conflict occurs and the corresponding Edit and Info symbol
of a previous connected
Push button or Digital Input Module
will be changed to black. In that case,
disconnect your last connected
Push button
, change the DIP switch settings to solve the address
conflict and reconnect the
Push button
again. If the conflict is solved, all connected devices will now
appear on the Peripherals page and their Edit and Info Symbol will be red.
y
The Peripheral page is not automatically refreshed, so you need to refresh it by clicking the peripheral
TAB again (or push [F5] or press <CTRL-R> on your keyboard if you use Internet Explorer or Mozilla
Firefox).