Tab.7
List of parameters CP: Circuits Parameters = Parameters for the heating circuit
Parameter
Description
Factory setting
Factory setting
Heating water flow temperature set point for the area heated if no
outside temperature sensor has been connected.
For the PCB: Can be set from 7 to 90°C.
For the PCB: Can be set from 7 to 100°C.
75°C
40°C
Post-operation time of the generator pump.
Can be set from 0 to 20 minutes.
3 minutes
not available
Room temperature set point in reduced mode.
Can be set from 5 to 30°C.
16°C
16°C
Room temperature set point in comfort mode.
Can be set from 5 to 30°C.
20°C
20°C
Do not modify this setting.
6°C
6°C
Do not modify this setting.
21°C
21°C
Do not modify this setting.
22°C
22°C
Do not modify this setting.
20°C
20°C
Circuit operating mode:
= timer programming
= manual mode
= frost protection mode
0
0
Do not modify this setting.
not available
55°C
Do not modify this setting.
not available
10°C
Temperature set point for SWIMMING POOL mode.
not available
20°C
Do not modify this setting.
0
0
Tab.8
List of parameters DP: Direct Hot Water Parameters = Domestic hot water tank parameters
Parameter
Description
Factory setting
Factory setting
Do not modify this setting.
0
not available
Domestic hot water temperature set point in comfort mode.
Can be set from 40 to 65°C.
55°C
not available
Domestic hot water temperature set point in reduced mode.
Can be set from 10 to 60°C.
10°C
not available
Domestic hot water production mode:
= timer programming
= manual mode
= frost protection mode
0
not available
Post-circulation time for the pump after domestic hot water produc
tion:
Can be set from 0 to 60 minutes
set to 99 minutes = continuous running
3 minutes
not available
For more information, see
Browsing in the menus, page 18
8 Control panel settings IniControl 2
7626252 - v02 - 17102016
EF
25