SKG4 Gas Fired Humidifier
BACnet Communication Module User Guide
Page | 9
ID
Name
List
Description
W?
Notes
AV.110
Room RH Setpoint
Integrator
Value of the room relative humidity setpoint received from the network.
Present_Value
Out_of_Service
COV_Increment
0% RH to 100% RH, Resolution 0.10% RH
AV.111
Room RH Unoccupied
Setpoint
Integrator
Value of the room relative humidity reading received from the network
during no occupancy state.
Present_Value
Out_of_Service
COV_Increment
0% RH to 100% RH, Resolution 0.10% RH
AV.112
Room RH Vacant Setpoint
Integrator
Value of the room relative humidity reading received from the network
during vacancy.
Present_Value
Out_of_Service
COV_Increment
0% RH to 100% RH, Resolution 0.10% RH
AV.123
Room Demand
Integrator
Value of the humidity demand within the room.
Present_Value
Out_of_Service
COV_Increment
Relinquish_Default
0% to 100%, Resolution 0.01%
AV.125
Supply High Limit Network
Reading
Integrator
Value of the supply high limit reading received from the network.
Present_Value
Out_of_Service
COV_Increment
Relinquish_Default
0.00% to 100.00%, Resolution 0.01%
AV.126
Supply High Limit Setpoint
Integrator
Value of the supply high limit setpoint received from the network.
Present_Value
Out_of_Service
COV_Increment
0% RH to 100% RH, Resolution 0.10% RH
AV.139
Supply High Limit Demand
Integrator
Supply high limit humidity demand value.
Present_Value
Out_of_Service
COV_Increment
Relinquish_Default
0% to 100%, Resolution 0.01%
AV.141
Humidity Control Network
Demand
Integrator
Value of the humidity control demand received from the network.
Present_Value
Out_of_Service
COV_Increment
Relinquish_Default
0.00% to 100.00%, Resolution 0.1%
AV.142
Humidity Control Network
High Limit
Integrator
Value of the humidity control high limit received from the network.
Present_Value
Out_of_Service
COV_Increment
Relinquish_Default
0.00% to 100.00%, Resolution 0.01%
AV.146
Humidity Demand
Integrator
Value of the current humidity demand.
Out_of_Service
COV_Increment
Relinquish_Default
0% to 100%, Resolution 0.01%
AV.148
System Power Output
Integrator
Displays the measured power output of the system as a percentage of the
total power.
Out_of_Service
COV_Increment
0% to 100%, Resolution 0.01%
AV.150
Module 1 Chimney Temp
Integrator
Value of the flue gas temperature value of the first humidifier module.
Present_Value
Out_of_Service
COV_Increment
32.00°F to 500.00°F or 0.00°C to max: 260.00°C
Resolution 0.18°F or 0.10°C
AV.151
Module 1 Water Temp
Integrator
Value of temperature of water in the evaporation chamber of the first
humidifier module.
Out_of_Service
COV_Increment
Units
32°F to 257°F or 0°C to 125°C
Resolution 0.018°F or 0.01°C