SKG4 Gas Fired Humidifier
BACnet Communication Module User Guide
Page | 10
ID
Name
List
Description
W?
Notes
AV.152
Module 1 Water
Frequency
Integrator
Value of the input frequency of the water level sensor of the first humidifier
module.
Present_Value
Out_of_Service
COV_Increment
0Hz to 30000Hz, Resolution 1Hz
AV.154
Module 1 Ambient Temp
Integrator
Value of the temperature inside of the weather proof enclosure of the first
humidifier module.
Present_Value
Out_of_Service
COV_Increment
-40.00°F to 212.00°F or
-40.00°C to 100.00°C
Resolution 0.18°F or 0.10°C
AV.155
Module 1 Fan Feedback
Integrator
Value from the burner fan feedback of the first humidifier module,
Present_Value
Out_of_Service
COV_Increment
0 to 2000 Hz, Resolution 1 Hz
AV.156
Module 1 Fan PWM
Integrator
Value of the PWM control signal from the burner fan of the first humidifier
module.
Out_of_Service
COV_Increment
Relinquish_Default
0% to 100%, Resolution 0.10%
AV.158
Module 1 Run Time
Integrator
Value of the total runtime of the first humidifier module.
Out_of_Service
COV_Increment
0.00 hours to 21474836.47 hours,
Resolution 0.01 hours
AV.159
Module 1 Service On Time
Integrator
Value of the operating time of the first humidifier module, since the last
servicing.
Out_of_Service
COV_Increment
0.00 hours to 21474836.47 hours,
Resolution 0.01 hours
AV.160
Module 1 Service Run
Time
Integrator
Value of the runtime of the first humidifier module, since the last servicing.
Present_Value
Out_of_Service
COV_Increment
0.00 hours to 21474836.47 hours,
Resolution 0.01 hours
AV.161
Module 1 On Time
Integrator
Value of the total operating time for the first humidifier module
Out_of_Service
COV_Increment
0.00 hours to 21474836.47 hours,
Resolution 0.01 hours
AV.162
Module 1 Demand
Integrator
Value of the measured humidity demand of the first humidifier module.
Present_Value
Out_of_Service
COV_Increment
Relinquish_Default
0% to 100%, Resolution 1.00%
AV.166
Module 1 Max Steam
Output
Integrator
Configuration value of the maximum steam output of the first modulating
humidifier relative to its total capacity.
Present_Value
Out_of_Service
COV_Increment
0% to 100%, Resolution 5.00%
AV.170
Module 2 Chimney Temp
Integrator
Value of the flue gas temperature value of the second humidifier module.
Present_Value
Out_of_Service
COV_Increment
32.00°F to 500.00°F or 0.00°C to max: 260.00°C
Resolution 0.18°F or 0.10°C
AV.171
Module 2 Water Temp
Integrator
Value of temperature of water in the evaporation chamber of the second
humidifier module.
Out_of_Service
COV_Increment
Units
32°F to 257°F or 0°C to 125°C
Resolution 0.018°F or 0.01°C
AV.172
Module 2 Water
Frequency
Integrator
Value of the input frequency of the water level sensor of the second
humidifier module.
Present_Value
Out_of_Service
COV_Increment
0Hz to 30000Hz, Resolution 1Hz
AV.174
Module 2 Ambient Temp
Integrator
Value of the temperature inside of the weather proof enclosure of the
second humidifier module.
Present_Value
Out_of_Service
COV_Increment
-40.00°F to 212.00°F or
-40.00°C to 100.00°C
Resolution 0.18°F or 0.10°C