SKG4 Gas Fired Humidifier
BACnet Communication Module User Guide
Page | 14
ID
Name
List
Description
W?
Notes
AV.270
Humidity Demand Low
Dead Band
Integrator
Value of the lower limit deadband for the humidity demand.
Present_Value
Out_of_Service
COV_Increment
0% RH to 100%, Resolution 0.01%
AV.273
Module 1 Ignition Count
Integrator
Number of times that the first humidifier module has completed an ignition
cycle.
Present_Value
Out_of_Service
0 to 214748364, Resolution 1
AV.274
Module 2 Ignition Count
Integrator
Number of times that the second humidifier module has completed an
ignition cycle
Present_Value
Out_of_Service
0 to 214748364, Resolution 1
AV.275
Module 3 Ignition Count
Integrator
Number of times that the third humidifier module has completed an ignition
cycle
Present_Value
Out_of_Service
0 to 214748364, Resolution 1
AV.276
Module 4 Ignition Count
Integrator
Number of times that the fourth humidifier module has completed an
ignition cycle
Present_Value
Out_of_Service
0 to 214748364, Resolution 1
AV.281
HRL Temperature
Integrator
Value of the room temperature measured by the HRL24 controller.
Present_Value
Out_of_Service
COV_Increment
Relinquish_Default
Units
-40°F to 500°F or -40°C to 260°C
Resolution 0.18°F or 0.10°C
AV.282
HRL Humidity
Integrator
Value of the room humidity measured by the HRL24 controller.
Present_Value
Out_of_Service
COV_Increment
Relinquish_Default
Units
0% RH to 100% RH, Resolution 0.1% RH
AV.285
Runtime
Integrator
The number of seconds that the system has been powered on. This value
is reset every time the system is shut off.
Present_Value
Out_of_Service
COV_Increment
Relinquish_Default
Units
0 to 999999999 seconds, Resolution 1 second
AV.303
Module 1 Water
Temperature Offset
Integrator
Configuration value to set the temperature offset for the first evaporation
chamber water temperature value,
in order to adjust the reading of the
temperature sensor to the proper temperature.
Present_Value
Out_of_Service
COV_Increment
-18.00°F to 18.00°F or -10.00°C to max: 10.00°C
Resolution 0.018°F or 0.01°C
AV.304
Module 2 Water
Temperature Offset
Integrator
Configuration value to set the temperature offset for the second
evaporation chamber water temperature value,
in order to adjust the
reading of the temperature sensor to the proper temperature.
Present_Value
Out_of_Service
COV_Increment
-18.00°F to 18.00°F or -10.00°C to max: 10.00°C
Resolution 0.018°F or 0.01°C
AV.305
Module 3 Water
Temperature Offset
Integrator
Configuration value to set the temperature offset for the third evaporation
chamber water temperature value,
in order to adjust the reading of the
temperature sensor to the proper temperature.
Present_Value
Out_of_Service
COV_Increment
-18.00°F to 18.00°F or -10.00°C to max: 10.00°C
Resolution 0.018°F or 0.01°C
AV.306
Module 4 Water
Temperature Offset
Integrator
Configuration value to set the temperature offset for the fourth evaporation
chamber water temperature value,
in order to adjust the reading of the
temperature sensor to the proper temperature.
Present_Value
Out_of_Service
COV_Increment
-18.00°F to 18.00°F or -10.00°C to max: 10.00°C
Resolution 0.018°F or 0.01°C