SKG4 Gas Fired Humidifier
BACnet Communication Module User Guide
Page | 17
Binary Value (BV)
Table 7 - Object Table Information: Binary Value (BV)
ID
Name
List
Description
W?
Notes
BV.2
Alarm Buzzer
Integrator
Configuration value that enables or disables the alarm buzzer sound when there
is a system warning.
Present_Value
Out_of_Service
Minimum_Off_Time
Minimum_On_Time
0 = Normal
1 = Disabled
BV.33
Module 1 Burner Inlet
Pressure
Integrator Status value of the burner inlet air pressure switch of the first humidifier module.
Present_Value
Out_of_Service
Minimum_Off_Time
Minimum_On_Time
0 = Normal
1 = Blocked
BV.34
Module 1 Water Level Low
Integrator Status value for the resistive low water level sensor of the first humidifier module.
Out_of_Service
Minimum_Off_Time
Minimum_On_Time
0 = Inactive
1 = Active
BV.35
Module 1 Water Level High
Integrator
Status value for the resistive high water level sensor of the first humidifier
module.
Out_of_Service
Minimum_Off_Time
Minimum_On_Time
0 = Inactive
1 = Active
BV.36
Module 1 Foam Sensor
Integrator
Displays whether foam has been detected within the first evaporation chamber. If
Foam is displayed, it indicates that the Anti-Foaming Energy Conservation
(AFEC) system has detected foam.
Out_of_Service
Minimum_Off_Time
Minimum_On_Time
0 = NoFoam
1= Foam
BV.39
Module 1 Gas Valve
Integrator Status value of the gas valve of the first humidifier module.
Present_Value
Out_of_Service
Minimum_Off_Time
Minimum_On_Time
0 = Off
1 = On
BV.40
Module 1 Tank Water Valve
Integrator
Status value of the evaporation chamber water supply valve of the first humidifier
module.
Present_Value
Out_of_Service
Relinquish_Default
Minimum_Off_Time
Minimum_On_Time
0 = Off
1 = On
BV.41
Module 1 Water Level Valve
Integrator Status value of the water level sensor supply valve of the first humidifier module.
Present_Value
Out_of_Service
Relinquish_Default
Minimum_Off_Time
Minimum_On_Time
0 = Off
1 = On
BV.42
Module 1 Drain Cooler Valve
Integrator Status value of the internal drain cooler valve of the first humidifier module.
Present_Value
Out_of_Service
Relinquish_Default
Minimum_Off_Time
Minimum_On_Time
0 = Off
1 = On
BV.43
Module 1 Drain Pump
Integrator Status value of the drain pump of the first humidifier module.
Present_Value
Out_of_Service
Relinquish_Default
Minimum_Off_Time
Minimum_On_Time
0 = Off
1 = On