SKG4 Gas Fired Humidifier
BACnet Communication Module User Guide
Page | 18
ID
Name
List
Description
W?
Notes
BV.45
Module 1 Ignition Control
Integrator Status value of the ignition control module of the first humidifier module.
Relinquish_Default
Out_of_Service
Minimum_Off_Time
Minimum_On_Time
0 = Off
1 = On
BV.47
Module 1 Alarm LED
Integrator Status value for the alarm LED of the first humidifier module.
Present_Value
Relinquish_Default
Out_of_Service
Minimum_Off_Time
Minimum_On_Time
0 = Off
1 = On
BV.48
Module 2 Burner Inlet
Pressure
Integrator
Status value of the burner inlet air pressure switch of the second humidifier
module.
Present_Value
Out_of_Service
Minimum_Off_Time
Minimum_On_Time
0 = Normal
1 = Blocked
BV.49
Module 2 Water Level Low
Integrator
Status value for the resistive low water level sensor of the second humidifier
module.
Out_of_Service
Minimum_Off_Time
Minimum_On_Time
0 = Inactive
1 = Active
BV.50
Module 2 Water Level High
Integrator
Status value for the resistive high water level sensor of the second humidifier
module.
Out_of_Service
Minimum_Off_Time
Minimum_On_Time
0 = Inactive
1 = Active
BV.51
Module 2 Foam Sensor
Integrator
Displays whether foam has been detected within the second evaporation
chamber. If Foam is displayed, it indicates that the Anti-Foaming Energy
Conservation (AFEC) system has detected foam.
Out_of_Service
Minimum_Off_Time
Minimum_On_Time
0 = NoFoam
1= Foam
BV.54
Module 2 Gas Valve
Integrator Status value of the gas valve of the second humidifier module.
Present_Value
Out_of_Service
Minimum_Off_Time
Minimum_On_Time
0 = Off
1 = On
BV.55
Module 2 Tank Water Valve
Integrator
Status value of the evaporation chamber water supply valve of the second
humidifier module.
Present_Value
Out_of_Service
Relinquish_Default
Minimum_Off_Time
Minimum_On_Time
0 = Off
1 = On
BV.56
Module 2 Water Level Valve
Integrator
Status value of the water level sensor supply valve of the second humidifier
module.
Present_Value
Out_of_Service
Relinquish_Default
Minimum_Off_Time
Minimum_On_Time
0 = Off
1 = On
BV.57
Module 2 Drain Cooler Valve
Integrator Status value of the internal drain cooler valve of the second humidifier module.
Present_Value
Out_of_Service
Relinquish_Default
Minimum_Off_Time
Minimum_On_Time
0 = Off
1 = On