SKG4 Gas Fired Humidifier
BACnet Communication Module User Guide
Page | 19
ID
Name
List
Description
W?
Notes
BV.58
Module 2 Drain Pump
Integrator Status value of the drain pump of the second humidifier module.
Present_Value
Out_of_Service
Relinquish_Default
Minimum_Off_Time
Minimum_On_Time
0 = Off
1 = On
BV.60
Module 2 Ignition Control
Integrator Status value of the ignition control module of the second humidifier module.
Relinquish_Default
Out_of_Service
Minimum_Off_Time
Minimum_On_Time
0 = Off
1 = On
BV.62
Module 2 Alarm LED
Integrator Status value for the alarm LED of the second humidifier module.
Present_Value
Relinquish_Default
Out_of_Service
Minimum_Off_Time
Minimum_On_Time
0 = Off
1 = On
BV.63
Module 3 Burner Inlet
Pressure
Integrator Status value of the burner inlet air pressure switch of the third humidifier module.
Present_Value
Out_of_Service
Minimum_Off_Time
Minimum_On_Time
0 = Normal
1 = Blocked
BV.64
Module 3 Water Level Low
Integrator Status value for the resistive low water level sensor of the third humidifier module.
Out_of_Service
Minimum_Off_Time
Minimum_On_Time
0 = Inactive
1 = Active
BV.65
Module 3 Water Level High
Integrator
Status value for the resistive high water level sensor of the third humidifier
module.
Out_of_Service
Minimum_Off_Time
Minimum_On_Time
0 = Inactive
1 = Active
BV.66
Module 3 Foam Sensor
Integrator
Displays whether foam has been detected within the third evaporation chamber. If
Foam is displayed, it indicates that the Anti-Foaming Energy Conservation
(AFEC) system has detected foam.
Out_of_Service
Minimum_Off_Time
Minimum_On_Time
0 = NoFoam
1= Foam
BV.69
Module 3 Gas Valve
Integrator Status value of the gas valve of the third humidifier module.
Present_Value
Out_of_Service
Minimum_Off_Time
Minimum_On_Time
0 = Off
1 = On
BV.70
Module 3 Tank Water Valve
Integrator
Status value of the evaporation chamber water supply valve of the third humidifier
module.
Present_Value
Out_of_Service
Relinquish_Default
Minimum_Off_Time
Minimum_On_Time
0 = Off
1 = On
BV.71
Module 3 Water Level Valve
Integrator Status value of the water level sensor supply valve of the third humidifier module.
Present_Value
Out_of_Service
Relinquish_Default
Minimum_Off_Time
Minimum_On_Time
0 = Off
1 = On