SKG4 Gas Fired Humidifier
BACnet Communication Module User Guide
Page | 20
ID
Name
List
Description
W?
Notes
BV.72
Module 3 Drain Cooler Valve
Integrator Status value of the internal drain cooler valve of the third humidifier module.
Present_Value
Out_of_Service
Relinquish_Default
Minimum_Off_Time
Minimum_On_Time
0 = Off
1 = On
BV.73
Module 3 Drain Pump
Integrator Status value of the drain pump of the third humidifier module.
Present_Value
Out_of_Service
Relinquish_Default
Minimum_Off_Time
Minimum_On_Time
0 = Off
1 = On
BV.75
Module 3 Ignition Control
Integrator Status value of the ignition control module of the third humidifier module.
Relinquish_Default
Out_of_Service
Minimum_Off_Time
Minimum_On_Time
0 = Off
1 = On
BV.77
Module 3 Alarm LED
Integrator Status value for the alarm LED of the third humidifier module.
Present_Value
Relinquish_Default
Out_of_Service
Minimum_Off_Time
Minimum_On_Time
0 = Off
1 = On
BV.78
Module 4 Burner Inlet
Pressure
Integrator Status value of the burner inlet air pressure switch of the third humidifier module.
Present_Value
Out_of_Service
Minimum_Off_Time
Minimum_On_Time
0 = Normal
1 = Blocked
BV.79
Module 4 Water Level Low
Integrator
Status value for the resistive low water level sensor of the fourth humidifier
module.
Out_of_Service
Minimum_Off_Time
Minimum_On_Time
0 = Inactive
1 = Active
BV.80
Module 4 Water Level High
Integrator
Status value for the resistive high water level sensor of the fourth humidifier
module.
Out_of_Service
Minimum_Off_Time
Minimum_On_Time
0 = Inactive
1 = Active
BV.81
Module 4 Foam Sensor
Integrator
Displays whether foam has been detected within the fourth evaporation chamber.
If Foam is displayed, it indicates that the Anti-Foaming Energy Conservation
(AFEC) system has detected foam.
Out_of_Service
Minimum_Off_Time
Minimum_On_Time
0 = NoFoam
1= Foam
BV.84
Module 4 Gas Valve
Integrator Status value of the gas valve of the fourth humidifier module.
Present_Value
Out_of_Service
Minimum_Off_Time
Minimum_On_Time
0 = Off
1 = On
BV.85
Module 4 Tank Water Valve
Integrator
Status value of the evaporation chamber water supply valve of the fourth
humidifier module.
Present_Value
Out_of_Service
Relinquish_Default
Minimum_Off_Time
Minimum_On_Time
0 = Off
1 = On