SKG4 Gas Fired Humidifier
BACnet Communication Module User Guide
Page | 22
ID
Name
List
Description
W?
Notes
BV.104
Network Control State
Integrator
Indicates the state of the control communication between the device and the
BACnet network.
Present_Value
Out_of_Service
Minimum_Off_Time
Minimum_On_Time
0 = Normal
1 = Fault
BV.105
Module 2 Foam State
Integrator
Displays whether the second humidifier module has currently detected foam or
not. If foam has been detected, the humidifier will perform a drain cycle.
Read Only
0 = Ok
1 = Detected
BV.106
Module 3 Foam State
Integrator
Displays whether the third humidifier module has currently detected foam or not.
If foam has been detected, the humidifier will perform a drain cycle.
Read Only
0 = Ok
1 = Detected
BV.107
Module 4 Foam State
Integrator
Displays whether the fourth humidifier module has currently detected foam or not.
If foam has been detected, the humidifier will perform a drain cycle.
Read Only
0 = Ok
1 = Detected
BV.109
HRL Lock Setpoint
Integrator Select whether the setpoint obtained from the HRL24 controller can be modified.
Present_Value
Relinquish_Default
Out_of_Service
Minimum_Off_Time
Minimum_On_Time
0 = Unlock
1= Lock
BV.111
Module 1 Drain Valve
Integrator Status value of the normally open drain valve of the first humidifier module.
Present_Value
Out_of_Service
Relinquish_Default
Minimum_Off_Time
Minimum_On_Time
0 = On
1 = Off
BV.112
Module 2 Drain Valve
Integrator Status value of the normally open drain valve of the second humidifier module.
Present_Value
Out_of_Service
Relinquish_Default
Minimum_Off_Time
Minimum_On_Time
0 = On
1 = Off
BV.113
Module 3 Drain Valve
Integrator Status value for the normally open drain valve of the third humidifier module.
Present_Value
Out_of_Service
Relinquish_Default
Minimum_Off_Time
Minimum_On_Time
0 = On
1 = Off
BV.114
Module 4 Drain Valve
Integrator Status value for the normally open drain valve fourth humidifier module.
Present_Value
Out_of_Service
Relinquish_Default
Minimum_Off_Time
Minimum_On_Time
0 = On
1 = Off
BV.119
Inhibit Resistive Probe 1
Integrator
Select whether to disable the resistive water level sensor probes or not for the
first humidifier module. When performing a manual calibration procedure for the
water level sensor or when using the ultrapure humidifier option, this setting must
be set to
Yes
.
Present_Value
Out_of_Service
Minimum_Off_Time
Minimum_On_Time
0 = No
1 = Yes
BV.120
Inhibit Resistive Probe 2
Integrator
Select whether to disable the resistive water level sensor probes or not for the
second humidifier module. When performing a manual calibration procedure for
the water level sensor or when using the ultrapure humidifier option, this setting
must be set to
Yes
.
Present_Value
Out_of_Service
Minimum_Off_Time
Minimum_On_Time
0 = No
1 = Yes