SKG4 Gas Fired Humidifier
BACnet Communication Module User Guide
Page | 25
Multi State Value (MSV)
Table 9 - Object Table Information: Multi State Value (MSV)
ID
Name
List
Description
W?
Notes
MSV.9
BACnet Server List Mode
Integrator Configuration value to select the category of BACnet objects to display.
Present_Value
Out_of_Service
1 = Integrator
2 = Advanced
3 = Factory
MSV.10
BACnet Server Units
Integrator Configuration value to select the display units for the BACnet server.
Present_Value
Out_of_Service
1 = Metric
2 = Imperial
MSV.33
Control Profile
Integrator
Configuration value to select a preconfigured control mode profile for the
modulating humidity demand. Select the Custom option to configure individual
settings.
Present_Value
Out_of_Service
1 = ExternAnalog
2 = ExternNetwork
3 = InternAnalog
4 = InternNetwork
5 = HRL
6 = Custom
MSV.34
Modulating High Limit Profile
Integrator
Configuration value to select a preconfigured control mode profile for the
modulating high limit demand. Select the Custom option to configure individual
settings.
Present_Value
Out_of_Service
1 = Disabled
2 = ExternAnalog
3 = ExternNetwork
4 = InternAnalog
5 = InternNetwork
6 = Custom
MSV.37
Occupancy State
Integrator Displays the current occupancy state.
Out_of_Service
1 = Occupied
2 = Unoccupied
3 = Vacant
4 = Off
MSV.38
Room RH Source
Integrator Configuration value to select the reading source for the room demand.
Present_Value
Out_of_Service
1 = None
2 = RoomRH
3 = Network
MSV.39
Room RH Setpoint Source
Integrator Configuration value to select the room demand setpoint source.
Present_Value
Out_of_Service
1 = None
2 = Internal
3 = ControlInput
MSV.43
Supply High Limit Reading
Source
Integrator Configuration value to select the reading source for the supply high limit demand.
Present_Value
Out_of_Service
1 = None
2 = SupplyHLRH
3 = Network
MSV.44
Supply High Limit Setpoint
Source
Integrator Configuration value to select the supply high limit demand setpoint source.
Present_Value
Out_of_Service
1 = None
2 = Internal
3 = ControlInput
MSV.48
Humidity Control Demand
Source
Integrator Configuration value to select the humidity control demand source.
Present_Value
Out_of_Service
1 = None
2 = ControlInput
3 = RoomDemand
4 = Network
MSV.49
Humidity Control High Limit
Source
Integrator Configuration value to select the humidity control high limit source.
Present_Value
Out_of_Service
1 = None
2 = ControlInput
3 = SupplyHLDemand
4 = Network