SKG4 Gas Fired Humidifier
BACnet Communication Module User Guide
Page | 26
ID
Name
List
Description
W?
Notes
MSV.56
Humidity Control Cutout State
Integrator
Displays the current state of the safety control circuit and whether the circuit has
been disconnected due to a safety switch.
Out_of_Service
1 = Off
2 = Normal
3 = LowLimit
4 = HighLimit
5 = AirFlow
6 = Interlock
MSV.60
System Power State
Integrator Displays whether the system is powered on or off.
Present_Value
Out_of_Service
1 = Off
2 = On
MSV.61
System Request
Integrator
Select whether to perform one of the following actions for the system: reset service
counters, initiate a drain cycle, reset warning alarms, fill the evaporation chamber,
calibrate the water level sensor or perform an air purge.
Present_Value
Out_of_Service
1 = None
2 = Reset Alarms
3 = Drain
4 = Reset Counters
5 = Filling
6 = WaterCalib
7 = PurgeAir
MSV.63
Module 1 State
Integrator Displays the current state of operation of the first humidifier module.
Out_of_Service
1 = Off
2 = Idle
3 = LineRinse
4 = TankRinse
5 = Filling
6 = Draining
7 = Heating
8 = Boiling
9 = Alarm
10 = PurgeAir
MSV.64
Module 1 Request
Integrator
Select whether to perform one of the following actions for the first humidifier
module: reset service counters, initiate a drain cycle, reset warning alarms, fill the
evaporation chamber, calibrate the water level sensor or perform an air purge.
Present_Value
Out_of_Service
1 = None
2 = Reset Alarms
3 = Drain
4 = Reset Counters
5 = Filling
6 = WaterCalib
7 = PurgeAir