SKG4 Gas Fired Humidifier
BACnet Communication Module User Guide
Page | 28
ID
Name
List
Description
W?
Notes
MSV.68
Module 2 Alarm
Integrator
Displays the current status of the second humidifier’s alarm.
Out_of_Service
1 = Normal
2 = FailedPump
3 = FillTimeout
4 = Blocked Piping
5 = HeatTimeout
6 = Overheat
7 = WaterLeak
8 = Service
9 = Foaming
10 = BurnerLocked
11 = FanDefect
12 = FailedComm
13 = ChimTempHi
14 = RefillTimeout
15 = FanBlocked
16 = SystBlck
17 = TankBlocked
18 = RefillDelay
MSV.69
Module 3 State
Integrator Displays the current state of operation of the third humidifier module.
Out_of_Service
1 = Off
2 = Idle
3 = LineRinse
4 = TankRinse
5 = Filling
6 = Draining
7 = Heating
8 = Boiling
9 = Alarm
10 = PurgeAir
MSV.70
Module 3 Request
Integrator
Select whether to perform one of the following actions for the third humidifier
module: reset service counters, initiate a drain cycle, reset warning alarms, fill the
evaporation chamber, calibrate the water level sensor or perform an air purge.
Present_Value
Out_of_Service
1 = None
2 = Reset Alarms
3 = Drain
4 = Reset Counters
5 = Filling
6 = WaterCalib
7 = PurgeAir