SKG4 Gas Fired Humidifier
BACnet Communication Module User Guide
Page | 30
ID
Name
List
Description
W?
Notes
MSV.74
Module 4 Alarm
Integrator
Displays the current status of the fourth humidifier’s alarm.
Out_of_Service
1 = Normal
2 = FailedPump
3 = FillTimeout
4= Blocked Piping
5 = HeatTimeout
6 = Overheat
7 = WaterLeak
8 = Service
9 = Foaming
10 = BurnerLocked
11 = FanDefect
12 = FailedComm
13 = ChimTempHi
14 = RefillTimeout
15 = FanBlocked
16 = SystBlck
17 = TankBlocked
18 = RefillDelay
MSV.77
Boiler Fill Mode
Integrator
Configuration value to select the water filling method for the fill valve:
When set to OneShot, water will continuously flow.
When set to Pulsed, water will flow in short bursts.
Present_Value
Out_of_Service
1 = OneShot
2 = Pulsed
MSV.79
Boiler Idle Tank Rinse Off
Integrator
Configuration value to define whether to enable automatic rinse cycles while the
humidifier is turned off and remains inactive. To select the amount of time the
humidifier remains inactive before a rinse cycle is performed, configure the value
of the
Boiler Idle Tank Rinse Interval
setting.
Present_Value
Out_of_Service
1 = Off
2 = On
MSV.80
Boiler Idle Tank Rinse On
Integrator
Configuration value to define whether to enable automatic rinse cycles while the
humidifier is turned on and remains in “Idle” or stand-by mode. To select the
amount of time the humidifier remains inactive before a rinse cycle is performed,
configure the value of the
Boiler Idle Tank Rinse Interval
setting.
Present_Value
Out_of_Service
1 = Off
2 = On
MSV.93
Water Probe 1 Auto Calib
Integrator
Configuration value to set the frequency of the auto calibration setting for the water
level sensor of the first humidifier module.
Present_Value
Out_of_Service
1 = None
2 = Once
3 = Always
MSV.94
Water Probe 2 Auto Calib
Integrator
Configuration value to set the frequency of the auto calibration setting for the water
level sensor of the second humidifier module.
Present_Value
Out_of_Service
1 = None
2 = Once
3 = Always
MSV.95
Water Probe 3 Auto Calib
Integrator
Configuration value to set the frequency of the auto calibration setting for the water
level sensor of the third humidifier module.
Present_Value
Out_of_Service
1 = None
2 = Once
3 = Always
MSV.96
Water Probe 4 Auto Calib
Integrator
Configuration value to set the frequency of the auto calibration setting for the water
level sensor of the fourth humidifier module.
Present_Value
Out_of_Service
1 = None
2 = Once
3 = Always
MSV.99
System Mode
Integrator
Configuration value to set under which system operation mode the different
modules will operate.
Present_Value
Out_of_Service
1 = Parallel
2 = Sequential
3 = Hybrid
MSV.104 BACnet Server Language
Integrator Value of the BACnet server language.
Present_Value
Out_of_Service
1 = English