SKG4 Gas Fired Humidifier
BACnet Communication Module User Guide
Page | 31
ID
Name
List
Description
W?
Notes
MSV.115 Boiler Startup Tank Rinse
Integrator
Configuration value to define whether to perform an automatic rinse cycle upon
each start-up of the humidifier.
Present_Value
Out_of_Service
1 = Off
2 = On
MSV.116
Module 1 Water Level Probe
Warning
Integrator
Displays whether there is currently a warning message associated with the water
level sensor for the first humidifier module, in order to indicate that there is a
calibration error or a drifting error with the capacitive probe.
Read Only
1 = Ok
2 = Calib
3 = Replace
MSV.117
Module 2 Water Level Probe
Warning
Integrator
Displays whether there is currently a warning message associated with the water
level sensor for the second humidifier module, in order to indicate that there is a
calibration error or a drifting error with the capacitive probe.
Read Only
1 = Ok
2 = Calib
3 = Replace
MSV.118
Module 3 Water Level Probe
Warning
Integrator
Displays whether there is currently a warning message associated with the water
level sensor for the third humidifier module, in order to indicate that there is a
calibration error or a drifting error with the capacitive probe.
Read Only
1 = Ok
2 = Calib
3 = Replace
MSV.119
Module 4 Water Level Probe
Warning
Integrator
Displays whether there is currently a warning message associated with the water
level sensor for the fourth humidifier module, in order to indicate that there is a
calibration error or a drifting error with the capacitive probe.
Read Only
1 = Ok
2 = Calib
3 = Replace
MSV.121 Water Level 1 Probe Failure
Integrator
Displays which one of the water level sensor’s probes is currently not functioning
properly for the first humidifier module.
Read Only
1 = None
2 = Capacitive
3 = Resistive
4 = Both
MSV.122 Water Level 2 Probe Failure
Integrator
Displays which one of the water level sensor’s probes is currently not functioning
properly for the second humidifier module.
Read Only
1 = None
2 = Capacitive
3 = Resistive
4 = Both
MSV.123 Water Level 3 Probe Failure
Integrator
Displays which one of the water level sensor’s probes is currently not functioning
properly for the third humidifier module.
Read Only
1 = None
2 = Capacitive
3 = Resistive
4 = Both
MSV.124 Water Level 4 Probe Failure
Integrator
Displays which one of the water level sensor’s probes is currently not functioning
properly for the fourth humidifier module.
Read Only
1 = None
2 = Capacitive
3 = Resistive
4 = Both