SKG4 Gas Fired Humidifier
BACnet Communication Module User Guide
Page | 7
Object
Type
Enabled
Optional Properties
Supported
Writable Properties
Notes
Multi-
State
Input
•
Description
•
Reliability
•
State_Text
•
Out_of_Service
Multi-
State
Output
•
Description
•
Reliability
•
State_Text
•
Present_Value
•
Out_of_Service
•
Relinquish_Default
Program
•
Description
•
Reliability
•
Program_Change
•
Out_of_Service
Only LOAD and RESTART are supported for
program change. Use LOAD to apply the new
firmware.
Schedule
•
Description
•
Weekly_Schedule
•
Effective_Period
•
Schedule_Default
•
List_of_Object_Property
_References
•
Priority_for_Writing
•
Out_of_Service
•
Weekly_Schedule
If Out_of_Service is True, Present_Value becomes
writable.
Multi-
State
Value
•
Description
•
Reliability
•
States_Text
•
Priority_Array
•
Relinquish_Default
•
Present_Value
•
Relinquish_Default
•
Out_of_Service
Character
String
Value
•
Description
•
Present_Value
Date
•
Description
•
Reliability
•
Event_State
•
Out_of_Service
•
Present_Value
•
Out_of_Service
DateTime
•
Description
•
Reliability
•
Event_State
•
Out_of_Service
•
Present_Value
•
Out_of_Service
Positive-
Integer
Value
•
Description
•
Reliability
•
Event_State
•
Out_of_Service
•
Priority_Array
•
Relinquish_Default
•
Minimum_Present_Value
•
Maximum_Present_Value
•
Present_Value
•
Units
•
Out_of_Service
•
Relinquish_Default
Time
•
Description
•
Reliability
•
Event_State
•
Out_of_Service
•
Present_Value
•
Out_of_Service
Out_of_Service Property
Neptronic humidifiers offer the use of the Out_of_Service writable property. When the value of this property is set to
True, it disconnects the object from the physical input, enabling you to input other values. This is useful for special
applications or while troubleshooting. For example, you can ignore the temperature read from a sensor and input the
desired temperature value in order to perform specific tests.
Warning: If the Out_of_Service property is set to True, Out_of_Service remains true until set to False.