SKG4 Gas Fired Humidifier
BACnet Communication Module User Guide
Page | 23
ID
Name
List
Description
W?
Notes
BV.121
Inhibit Resistive Probe 3
Integrator
Select whether to disable the resistive water level sensor probes or not for the
third humidifier module. When performing a manual calibration procedure for the
water level sensor or when using the ultrapure humidifier option, this setting must
be set to
Yes
.
Present_Value
Out_of_Service
Minimum_Off_Time
Minimum_On_Time
0 = No
1 = Yes
BV.122
Inhibit Resistive Probe 4
Integrator
Select whether to disable the resistive water level sensor probes or not for the
fourth humidifier module. When performing a manual calibration procedure for the
water level sensor or when using the ultrapure humidifier option, this setting must
be set to
Yes
.
Present_Value
Out_of_Service
Minimum_Off_Time
Minimum_On_Time
0 = No
1 = Yes
BV.123
Module 1 Water Level Probe
Alarm
Integrator
Displays whether there is currently an alarm message to indicate that the water
level sensor is defective and must be replaced for the first humidifier module.
Read Only
0= Ok
1= Defect
BV.124
Module 2 Water Level Probe
Alarm
Integrator
Displays whether there is currently an alarm message to indicate that the water
level sensor is defective and must be replaced for the second humidifier module.
Read Only
0= Ok
1= Defect
BV.125
Module 3 Water Level Probe
Alarm
Integrator
Displays whether there is currently an alarm message to indicate that the water
level sensor is defective and must be replaced for the third humidifier module.
Read Only
0= Ok
1= Defect
BV.126
Module 4 Water Level Probe
Alarm
Integrator
Displays whether there is currently an alarm message to indicate that the water
level sensor is defective and must be replaced for the fourth humidifier module.
Read Only
0= Ok
1= Defect
BV.129
SMTP SSL
Integrator
Select whether to use a secure socket layer encrypt the communication between
the device and the email server or to use the default socket. If turned to
On
,
SMTP Port value must be set to
587
and
SMTP Username
and
SMTP Password
settings must be filled out. If turned to Off, use SMTP Port
25
to use server
without login account or SMTP Port
587
if login details for email account have
been entered.
Present_Value
Out_of_Service
Minimum_Off_Time
Minimum_On_Time
0 = Off
1 = On
BV.130
SMTP Port
Integrator
Select the port number to be used for email transfer. If set to
25
, server to server
email transfer is enabled (can only be used if SMTP SSL is set to
Off
). If set to
587
, client to server email transfer is enabled.
Present_Value
Out_of_Service
Minimum_Off_Time
Minimum_On_Time
0 = 25
1 = 587
BV.131
Notify Alarm
Integrator
Select whether to get notified of all humidifier alarm messages by email.
Present_Value
Out_of_Service
Minimum_Off_Time
Minimum_On_Time
0 = Off
1 = On
BV.132
Notify Warning
Integrator Select whether to get notified of all humidifier warning messages by email.
Present_Value
Out_of_Service
Minimum_Off_Time
Minimum_On_Time
0 = Off
1 = On
BV.133
Notify App Msg
Integrator Select whether to get notified of all humidifier event messages by email.
Present_Value
Out_of_Service
Minimum_Off_Time
Minimum_On_Time
0 = Off
1 = On