BACnet Properties Configuration 

To establish communication on the network, and guarantee a unique ID of devices in a BACnet system, the following 
properties may have to be configured.  

Table 1 - BACnet Properties Configuration 

Property 

Default Value 

Configuration 

MAC Address 

001 

 

Set to a unique address on the network between 000 and 254. 

 

The value can be set manually via the menu. 

 

The values from 128-254 represent MS/TP non-token passing slave 
devices. 

Device Instance 

Auto 

 

The humidifier automatically configures its device instance to 153,000 + 
MAC address.  

 

The value can be set manually via the menu. 

 

The value can be set manually through the 

WriteProperty

 service to 

Device Object.Object_Identifier

.  

 

The device’s 

Object_Identifier

 is a combination of the 

Device 

Object_Type

 (8) and the 

Device_Instance

 (0-4194302), therefore its 

decimal or hexadecimal representation tends to be incomprehensible. 

 

For example, the 

Device_Instance

=1000 has an equivalent 

Object_Identifier

 of 0x020003E8 hexadecimal or 33555432 decimal. 

Baud Rate 

0 = Auto 

 

The humidifier configures its baud rate automatically by detecting the 
network upon connection. 

 

The value can be set manually from the available values of (0) Auto, 9600, 
19200, 38400, and 76800. 

Max_Master 

127 

 

Configure 

Max_Master

 value to increase network efficiency when there are 

less than 127 devices on the network.  

 

The 

Max_Master

 value can be changed through the 

WriteProperty 

service 

to

 Device

 

Object.Max_Master

For more information, refer to the

 

MAC Address and Max_Master

 

section.  

Device Object.Object_Name 

Name of the 

device 

 

Configure the name of the device through the 

WriteProperty 

service to 

Device Object.Object_Name

. For example, SKG4. 

 

 

 

Summary of Contents for Bacnet SKG4

Page 1: ...SKG4 BACnet Guide 191017 SKG4 Gas Fired Humidifier BACnet Communication Module User Guide...

Page 2: ...ACnet Properties Configuration 2 Configuration Options 3 Quick Setup 3 Manual Setup 3 IP Port 4 Network Reset 4 Device Object Properties 5 Object Types Supported 6 Out_of_Service Property 7 Object Tab...

Page 3: ...s to ensure a Tusage_timeout value within 20 minutes MS TP Support The humidifier supports a Full Master Node state machine for MS TP The Max_Master and the instances are configured to the device obje...

Page 4: ...dentifier The device s Object_Identifier is a combination of the Device Object_Type 8 and the Device_Instance 0 4194302 therefore its decimal or hexadecimal representation tends to be incomprehensible...

Page 5: ...ot guarantee efficient operation of the humidifier and other MS TP units on the MS TP network Some MAC address and Max_Master combinations are more efficient than others BACnet requires token passing...

Page 6: ...x_Master the maximum MAC address in the system If consecutive numbering is not possible then the next most efficient setup is one in which all units have Max_Master the maximum MAC address in the syst...

Page 7: ...on APDU_Timeout 3 000 W Number_of_APDU_Retries Always 3 Local_Time 00 00 00 W Local_Date 01 Jan 2015 Thu W UtC_Offset 300 minutes W Daylight_Savings_Status False W Backup_Failure_Timeout 10 W Configur...

Page 8: ...7 for more information Analog Output Description Reliability Min Pres Value Max Pres Value Resolution COV_Increment Present_Value COV_Increment Out_of_Service Relinquish_Default Units Binary Input Re...

Page 9: ...acter String Value Description Present_Value Date Description Reliability Event_State Out_of_Service Present_Value Out_of_Service DateTime Description Reliability Event_State Out_of_Service Present_Va...

Page 10: ...y high limit humidity reading Out_of_Service COV_Increment 0 RH to 100 RH Resolution 1 00 RH AV 54 Room RH Integrator Value of the room humidity reading Out_of_Service COV_Increment 0 RH to 100 RH Res...

Page 11: ...ue Out_of_Service COV_Increment 0 RH to 100 RH Resolution 0 10 RH AV 139 Supply High Limit Demand Integrator Supply high limit humidity demand value Present_Value Out_of_Service COV_Increment Relinqui...

Page 12: ...since the last servicing Present_Value Out_of_Service COV_Increment 0 00 hours to 21474836 47 hours Resolution 0 01 hours AV 161 Module 1 On Time Integrator Value of the total operating time for the...

Page 13: ...odule Present_Value Out_of_Service COV_Increment Relinquish_Default 0 to 100 Resolution 1 00 AV 186 Module 2 Max Steam Output Integrator Configuration value of the maximum steam output of the second m...

Page 14: ...rature value of the fourth humidifier module Present_Value Out_of_Service COV_Increment 32 00 F to 500 00 F or 0 00 C to max 260 00 C Resolution 0 18 F or 0 10 C AV 211 Module 4 Water Temp Integrator...

Page 15: ...oint for the evaporation chamber when there is no demand Present_Value Out_of_Service COV_Increment Units 32 F to 140 F or 0 C to 60 C Resolution 2 F or 1 C AV 236 Boiler Idle Time Drain Integrator Co...

Page 16: ...The number of seconds that the system has been powered on This value is reset every time the system is shut off Present_Value Out_of_Service COV_Increment Relinquish_Default Units 0 to 999999999 secon...

Page 17: ...humidifier is used Out_of_Service Polarity 0 0 1 100 BI 6 Interlock Integrator Displays the status of the interlock If the switch is Open it indicates that the humidifier is stopped as a result of th...

Page 18: ...Status value for the alarm warning relay Present_Value Out_of_Service Polarity Relinquish_Default Minimum_Off_Time Minimum_On_Time 0 Off 1 On BO 5 Alarm LED Integrator Status value for the alarm LED P...

Page 19: ...her foam has been detected within the first evaporation chamber If Foam is displayed it indicates that the Anti Foaming Energy Conservation AFEC system has detected foam Out_of_Service Minimum_Off_Tim...

Page 20: ...f the second humidifier module Out_of_Service Minimum_Off_Time Minimum_On_Time 0 Inactive 1 Active BV 51 Module 2 Foam Sensor Integrator Displays whether foam has been detected within the second evapo...

Page 21: ...l sensor of the third humidifier module Out_of_Service Minimum_Off_Time Minimum_On_Time 0 Inactive 1 Active BV 65 Module 3 Water Level High Integrator Status value for the resistive high water level s...

Page 22: ...ressure switch of the third humidifier module Present_Value Out_of_Service Minimum_Off_Time Minimum_On_Time 0 Normal 1 Blocked BV 79 Module 4 Water Level Low Integrator Status value for the resistive...

Page 23: ...e Minimum_On_Time 0 Off 1 On BV 94 Boiler Service Operation Integrator Select whether to enable the humidifier to continue producing steam even when it is due for servicing When set to Allowed the hum...

Page 24: ...humidifier module Present_Value Out_of_Service Relinquish_Default Minimum_Off_Time Minimum_On_Time 0 On 1 Off BV 112 Module 2 Drain Valve Integrator Status value of the normally open drain valve of t...

Page 25: ...el sensor is defective and must be replaced for the third humidifier module Read Only 0 Ok 1 Defect BV 126 Module 4 Water Level Probe Alarm Integrator Displays whether there is currently an alarm mess...

Page 26: ...address for the email account Present_Value CV 22 SMTP Mail From Integrator Set the email address that will be sending the humidifier notification messages Present_Value CV 24 SMTP Mail To Integrator...

Page 27: ...ExternAnalog 3 ExternNetwork 4 InternAnalog 5 InternNetwork 6 Custom MSV 37 Occupancy State Integrator Displays the current occupancy state Out_of_Service 1 Occupied 2 Unoccupied 3 Vacant 4 Off MSV 38...

Page 28: ...a drain cycle reset warning alarms fill the evaporation chamber calibrate the water level sensor or perform an air purge Present_Value Out_of_Service 1 None 2 Reset Alarms 3 Drain 4 Reset Counters 5...

Page 29: ...lck 17 TankBlocked 18 RefillDelay MSV 66 Module 2 State Integrator Displays the current state of operation of the second humidifier module Out_of_Service 1 Off 2 Idle 3 LineRinse 4 TankRinse 5 Filling...

Page 30: ...tBlck 17 TankBlocked 18 RefillDelay MSV 69 Module 3 State Integrator Displays the current state of operation of the third humidifier module Out_of_Service 1 Off 2 Idle 3 LineRinse 4 TankRinse 5 Fillin...

Page 31: ...lck 17 TankBlocked 18 RefillDelay MSV 72 Module 4 State Integrator Displays the current state of operation of the fourth humidifier module Out_of_Service 1 Off 2 Idle 3 LineRinse 4 TankRinse 5 Filling...

Page 32: ...n and remains in Idle or stand by mode To select the amount of time the humidifier remains inactive before a rinse cycle is performed configure the value of the Boiler Idle Tank Rinse Interval setting...

Page 33: ...order to indicate that there is a calibration error or a drifting error with the capacitive probe Read Only 1 Ok 2 Calib 3 Replace MSV 119 Module 4 Water Level Probe Warning Integrator Displays wheth...

Page 34: ...Program Change only LOAD 1 and RESTART 4 are supported PGM 8 Universal User Control Program Advanced Universal User Control Program Program_Change Out_of_Service Program Change only LOAD 1 and RESTAR...

Page 35: ...e 33 ID Name List Description W Notes SCH 2 Drain Schedule Integrator Customized draining schedule with up to six events per day Effective_Period Schedule_Default List_of_Object_Property_ References P...

Page 36: ...u blvd Montreal Qc H4N 1R6 Canada www neptronic com Toll free in North America 1 800 361 2308 Tel 514 333 1433 Fax 514 333 3163 Customer service fax 514 333 1091 Monday to Friday 8 00am to 5 00pm East...

Reviews: