SKG4 Gas Fired Humidifier 

BACnet Communication Module User Guide 

 

 

www.neptronic.com

 

Page | 6 

 

Object Types Supported 

The following table lists all the BACnet properties supported for each object type. Most of the  properties are locked. 
The exception is 

Present_Value

, which represents the dynamic operating values of the device, and the Status_Flag, 

Event_State

,

 and Reliability properties, which reflect the availability of the 

Present_Value

. Unless otherwise specified, 

properties are not changeable. 

Table 3 - Object Types Supported 

Object 

Type 

Enabled 

Optional Properties 

Supported 

Writable Properties 

Notes 

Note: Writable properties are different for some objects. Refer to the respective Object Table information to know the writable property for objects.

 

Analog 

Input 

 

  Reliability 

  Description 

  Min_Present_Value 

  Max_Present_Value 

  Resolution 

  COV_Increment 

  Out_of_Service 

  COV_Increment 

  Units

 

If "Out_of_Service" is true, Present_Value becomes 
a writable property. Refer to Out_of_Service 
Property section on page 7 for more information.  

Analog 

Value 

 

  Reliability 

  Description 

  Min_Present_Value 

  Max_Present_Value 

  Resolution 

  COV_Increment 

  Priority_Array 

  Relinquish_Default

 

  Present_Value  

  Out_of_Service 

  COV_Increment 

  Relinquish_Default 

  Units

 

Refer to Out_of_Service Property section on page 7 
for more information.  

Analog 

Output 

 

  Description 

  Reliability 

  Min-Pres-Value 

  Max-Pres-Value 

  Resolution 

  COV_Increment 

  Present_Value  

  COV_Increment 

  Out_of_Service 

  Relinquish_Default 

  Units 

 

Binary 

Input 

 

  Reliability 

  Active_Text 

  Inactive_Text 

  Description 

  Out_of_Service 

 

Polarity

 

  If "Out_of_Service" is true, Present_Value 

becomes a writable property. Refer to 
Out_of_Service Property section on page 7 for 
more information.  

Binary 

Value 

 

  Reliability 

  Active_Text 

  Inactive_Text 

  Description 

  Priority_Array 

  Relinquish_Default 

  Minimum_Off_Time 

  Minimum_On_Time

 

  Present_Value 

 

Out_of_Service

 

  Relinquish_Default 

  Minimum_Off_Time 

  Minimum_On_Time

 

Refer to Out_of_Service Property section on page 7 
for more information. 

Binary 

Output 

 

  Description 

  Reliability 

  Inactive-text 

  Active-text 

  Minimum_Off_Time 

  Minimum_On_Time

 

  Present_Value 

 

Out_of_Service

 

 

Polarity

 

  Relinquish_Default 

  Minimum_Off_Time 

  Minimum_On_Time

 

 

Device 

 

  Max_Master 

  Max_Info_Frame 

  Description 

  active-COV-subscriptions 

  Local_Time 

  Local_Date 

  UTC_Offset  

  Daylight_Savings_Status 

  Backup_Failure_Timeout 

  Configuration_Files 

  Last_Restore_Time 

  Backup_And_Restore_State 

  Backup_Preparation_Time 

  Restore_Completion_Time 

  Restore_Preparation_Time 

  Location 

  Serial_Number 

  Profile_Name

 

  Object_Identifier 

  Object_Name 

  Max_Master 

  Description 

  Local_Time 

  Local_Date 

  UTC_Offset  

  Daylight_Savings_Status 

  Apdu_Timeout 

  Backup_Failure_Timeout 

  Location

 

 

File 

 

  Description 

File_Size 

Only 0 is the accepted value to be written to the file 
size. 

Group 

 

  Description 

 

 

Summary of Contents for Bacnet SKG4

Page 1: ...SKG4 BACnet Guide 191017 SKG4 Gas Fired Humidifier BACnet Communication Module User Guide...

Page 2: ...ACnet Properties Configuration 2 Configuration Options 3 Quick Setup 3 Manual Setup 3 IP Port 4 Network Reset 4 Device Object Properties 5 Object Types Supported 6 Out_of_Service Property 7 Object Tab...

Page 3: ...s to ensure a Tusage_timeout value within 20 minutes MS TP Support The humidifier supports a Full Master Node state machine for MS TP The Max_Master and the instances are configured to the device obje...

Page 4: ...dentifier The device s Object_Identifier is a combination of the Device Object_Type 8 and the Device_Instance 0 4194302 therefore its decimal or hexadecimal representation tends to be incomprehensible...

Page 5: ...ot guarantee efficient operation of the humidifier and other MS TP units on the MS TP network Some MAC address and Max_Master combinations are more efficient than others BACnet requires token passing...

Page 6: ...x_Master the maximum MAC address in the system If consecutive numbering is not possible then the next most efficient setup is one in which all units have Max_Master the maximum MAC address in the syst...

Page 7: ...on APDU_Timeout 3 000 W Number_of_APDU_Retries Always 3 Local_Time 00 00 00 W Local_Date 01 Jan 2015 Thu W UtC_Offset 300 minutes W Daylight_Savings_Status False W Backup_Failure_Timeout 10 W Configur...

Page 8: ...7 for more information Analog Output Description Reliability Min Pres Value Max Pres Value Resolution COV_Increment Present_Value COV_Increment Out_of_Service Relinquish_Default Units Binary Input Re...

Page 9: ...acter String Value Description Present_Value Date Description Reliability Event_State Out_of_Service Present_Value Out_of_Service DateTime Description Reliability Event_State Out_of_Service Present_Va...

Page 10: ...y high limit humidity reading Out_of_Service COV_Increment 0 RH to 100 RH Resolution 1 00 RH AV 54 Room RH Integrator Value of the room humidity reading Out_of_Service COV_Increment 0 RH to 100 RH Res...

Page 11: ...ue Out_of_Service COV_Increment 0 RH to 100 RH Resolution 0 10 RH AV 139 Supply High Limit Demand Integrator Supply high limit humidity demand value Present_Value Out_of_Service COV_Increment Relinqui...

Page 12: ...since the last servicing Present_Value Out_of_Service COV_Increment 0 00 hours to 21474836 47 hours Resolution 0 01 hours AV 161 Module 1 On Time Integrator Value of the total operating time for the...

Page 13: ...odule Present_Value Out_of_Service COV_Increment Relinquish_Default 0 to 100 Resolution 1 00 AV 186 Module 2 Max Steam Output Integrator Configuration value of the maximum steam output of the second m...

Page 14: ...rature value of the fourth humidifier module Present_Value Out_of_Service COV_Increment 32 00 F to 500 00 F or 0 00 C to max 260 00 C Resolution 0 18 F or 0 10 C AV 211 Module 4 Water Temp Integrator...

Page 15: ...oint for the evaporation chamber when there is no demand Present_Value Out_of_Service COV_Increment Units 32 F to 140 F or 0 C to 60 C Resolution 2 F or 1 C AV 236 Boiler Idle Time Drain Integrator Co...

Page 16: ...The number of seconds that the system has been powered on This value is reset every time the system is shut off Present_Value Out_of_Service COV_Increment Relinquish_Default Units 0 to 999999999 secon...

Page 17: ...humidifier is used Out_of_Service Polarity 0 0 1 100 BI 6 Interlock Integrator Displays the status of the interlock If the switch is Open it indicates that the humidifier is stopped as a result of th...

Page 18: ...Status value for the alarm warning relay Present_Value Out_of_Service Polarity Relinquish_Default Minimum_Off_Time Minimum_On_Time 0 Off 1 On BO 5 Alarm LED Integrator Status value for the alarm LED P...

Page 19: ...her foam has been detected within the first evaporation chamber If Foam is displayed it indicates that the Anti Foaming Energy Conservation AFEC system has detected foam Out_of_Service Minimum_Off_Tim...

Page 20: ...f the second humidifier module Out_of_Service Minimum_Off_Time Minimum_On_Time 0 Inactive 1 Active BV 51 Module 2 Foam Sensor Integrator Displays whether foam has been detected within the second evapo...

Page 21: ...l sensor of the third humidifier module Out_of_Service Minimum_Off_Time Minimum_On_Time 0 Inactive 1 Active BV 65 Module 3 Water Level High Integrator Status value for the resistive high water level s...

Page 22: ...ressure switch of the third humidifier module Present_Value Out_of_Service Minimum_Off_Time Minimum_On_Time 0 Normal 1 Blocked BV 79 Module 4 Water Level Low Integrator Status value for the resistive...

Page 23: ...e Minimum_On_Time 0 Off 1 On BV 94 Boiler Service Operation Integrator Select whether to enable the humidifier to continue producing steam even when it is due for servicing When set to Allowed the hum...

Page 24: ...humidifier module Present_Value Out_of_Service Relinquish_Default Minimum_Off_Time Minimum_On_Time 0 On 1 Off BV 112 Module 2 Drain Valve Integrator Status value of the normally open drain valve of t...

Page 25: ...el sensor is defective and must be replaced for the third humidifier module Read Only 0 Ok 1 Defect BV 126 Module 4 Water Level Probe Alarm Integrator Displays whether there is currently an alarm mess...

Page 26: ...address for the email account Present_Value CV 22 SMTP Mail From Integrator Set the email address that will be sending the humidifier notification messages Present_Value CV 24 SMTP Mail To Integrator...

Page 27: ...ExternAnalog 3 ExternNetwork 4 InternAnalog 5 InternNetwork 6 Custom MSV 37 Occupancy State Integrator Displays the current occupancy state Out_of_Service 1 Occupied 2 Unoccupied 3 Vacant 4 Off MSV 38...

Page 28: ...a drain cycle reset warning alarms fill the evaporation chamber calibrate the water level sensor or perform an air purge Present_Value Out_of_Service 1 None 2 Reset Alarms 3 Drain 4 Reset Counters 5...

Page 29: ...lck 17 TankBlocked 18 RefillDelay MSV 66 Module 2 State Integrator Displays the current state of operation of the second humidifier module Out_of_Service 1 Off 2 Idle 3 LineRinse 4 TankRinse 5 Filling...

Page 30: ...tBlck 17 TankBlocked 18 RefillDelay MSV 69 Module 3 State Integrator Displays the current state of operation of the third humidifier module Out_of_Service 1 Off 2 Idle 3 LineRinse 4 TankRinse 5 Fillin...

Page 31: ...lck 17 TankBlocked 18 RefillDelay MSV 72 Module 4 State Integrator Displays the current state of operation of the fourth humidifier module Out_of_Service 1 Off 2 Idle 3 LineRinse 4 TankRinse 5 Filling...

Page 32: ...n and remains in Idle or stand by mode To select the amount of time the humidifier remains inactive before a rinse cycle is performed configure the value of the Boiler Idle Tank Rinse Interval setting...

Page 33: ...order to indicate that there is a calibration error or a drifting error with the capacitive probe Read Only 1 Ok 2 Calib 3 Replace MSV 119 Module 4 Water Level Probe Warning Integrator Displays wheth...

Page 34: ...Program Change only LOAD 1 and RESTART 4 are supported PGM 8 Universal User Control Program Advanced Universal User Control Program Program_Change Out_of_Service Program Change only LOAD 1 and RESTAR...

Page 35: ...e 33 ID Name List Description W Notes SCH 2 Drain Schedule Integrator Customized draining schedule with up to six events per day Effective_Period Schedule_Default List_of_Object_Property_ References P...

Page 36: ...u blvd Montreal Qc H4N 1R6 Canada www neptronic com Toll free in North America 1 800 361 2308 Tel 514 333 1433 Fax 514 333 3163 Customer service fax 514 333 1091 Monday to Friday 8 00am to 5 00pm East...

Reviews: