14
Neptronic
®
www.neptronic.com
Evaporative Humidification / Cooling System
Step 4 - Install Drain Pipework
The SK VAP Evaporative Module features an integrated drain and overflow which must be connected to the main
building drain with 3/4” (20mm) copper or stainless pipework. The drain assembly can be reversed to face in the
opposite direction to suit either left or right feed pipe-work. This drain assembly should be connected to the main building drain
via the 3/4” (20mm) connection. Drain line must be directed to an open drain. No drain trap is required. Risk of return from
main drain to overflow.
1
5
1
2
5
6
8
Drain pump
Integrated Overflow
3/4” (20mm) Drain Plumbing
(Not supplied)
3/4” (20mm) Tee