Maintenance Schedule
WARNING: This humidifier must be installed, operated and maintained in accordance with this manual.
Failure to do so could result in contamination that might cause Legionnaires’ disease which can be
fatal.
Although the SK VAP Humidification System requires very little maintenance, it does require servicing. The
procedure for this is outlined in this maintenance section and service schedule tables. Maintenance of the water
treatment systems should be carried out as per the instructions supplied with that equipment.
Service Schedule
The service schedule should be determined at commissioning. This will depend on the application, the water quality
and the system usage. The default is 200 hrs operation. The programming section contains details of how to adjust the
service schedule to suit the applications.
Refer to the software overview section for details on how to access this page.
1) The Service Delay is the number of running hours before servicing is required.
2) The Service Runtime is the number of running hours since the last service.
3) The Total Runtime is the total number of hours the humidifier has been in operation.
After the humidifier has been serviced the Runtime hours can be reset by pressing
k
button to enter edit mode and
then pressing and hold both the
UP
and
DONWN
buttons (see Step 21 in Programming Mode).
WARNING: The SK VAP system should not be electrically isolated for periods exceeding
24hrs as automatic flush and purge cycles will be disabled
.
If the system is turned off for prolonged periods, water stagnation might occur and bacterial
contamination result
, therefore the system, including any storage tanks or vessels should be drained and left dry.
Before putting the system back into service, a full risk assessment should be undertaken to ensure safe operation, with
particular attention paid to water supply quality.
The water pipe-work supplying the SK VAP should be purged carefully, avoiding the creation of aerosols by
splashing, and a water sample should be taken to ensure cleanliness. In the event that the humidifier contains any
residual water or has remained damp, and the temperature exceeded 68°F (20°C), the SK VAP should be cleaned and
disinfected. Refer to the cleaning, disinfection and descaling instructions in this manual.
Summary of Contents for SK VAP
Page 4: ...4 Neptronic www neptronic com Evaporative Humidification Cooling System...
Page 17: ...17 Neptronic Evaporative Humidification Cooling System www neptronic com Wiring Diagram...
Page 18: ...18 Neptronic www neptronic com Evaporative Humidification Cooling System...
Page 19: ...19 Neptronic Evaporative Humidification Cooling System www neptronic com...
Page 20: ...20 Neptronic www neptronic com Evaporative Humidification Cooling System...
Page 21: ...21 Neptronic Evaporative Humidification Cooling System www neptronic com...
Page 22: ...22 Neptronic www neptronic com Evaporative Humidification Cooling System...
Page 34: ...34 Neptronic www neptronic com Evaporative Humidification Cooling System...
Page 35: ...35 Neptronic Evaporative Humidification Cooling System www neptronic com...