6
Neptronic
®
www.neptronic.com
Evaporative Humidification / Cooling System
SK VAP Principle of Operation
Raising the relative humidity by passing air through a wetted matrix is a simple and safe way to humidify - with the
added benefits of very low running costs and evaporative cooling.
At the heart of the SK VAP is the evaporative module, which is installed in an AHU or duct. Water is supplied to the top
of a highly efficient bonded matrix, which is impregnated with silver for added hygiene. Dry air passes through this
moist material picking up water vapour, raising the humidity as it does so. This process consumes very little energy, far
less than steam humidifiers or even cold water atomisers.
The water that doesn’t evaporate assists in washing the matrix material and flows into a stainless steel tank at the base
of the unit before being re-circulated up onto the matrix again.
As each vertical matrix bank has its own water supply, multi-stage control is an option which individually operates sec-
tions of the system for closer control.
Modular construction facilitates a range of system sizes and efficiencies to match the requirements of individual appli-
cations, and ease of installation, maintenance and replacement should damage occur to any of the matrix casssettes.
To prevent clogging of the humidifier cassettes, the airflow into the module must be filtered to at least 5 micron filtration
standard. Finer filtration may be required for hospitals or where air is being supplied to areas where food or electronic
products are being handled.
To prevent droplet carry over an optional droplet separator can be fitted. It is recommended for velocities above
11.5 ft/s (3.5 m/s) when the fan is positioned before the SK VAP or velocities above 13 ft/s (4.0 m/s) when the fan is
positioned after it.
For areas of hard water, water treatment is recommended to reduce maintenance requirements.
Typical Installation
Please note that electrical Isolator,
module up stands, interconnecting
pipework and drain pan are not sup-
plied (shown dotted).
Air
Flow
Summary of Contents for SK VAP
Page 4: ...4 Neptronic www neptronic com Evaporative Humidification Cooling System...
Page 17: ...17 Neptronic Evaporative Humidification Cooling System www neptronic com Wiring Diagram...
Page 18: ...18 Neptronic www neptronic com Evaporative Humidification Cooling System...
Page 19: ...19 Neptronic Evaporative Humidification Cooling System www neptronic com...
Page 20: ...20 Neptronic www neptronic com Evaporative Humidification Cooling System...
Page 21: ...21 Neptronic Evaporative Humidification Cooling System www neptronic com...
Page 22: ...22 Neptronic www neptronic com Evaporative Humidification Cooling System...
Page 34: ...34 Neptronic www neptronic com Evaporative Humidification Cooling System...
Page 35: ...35 Neptronic Evaporative Humidification Cooling System www neptronic com...