SK300-XL Steam Humidifier
11
Stage 2 – Steam Distribution Installation
Steam pipe work to Duct connections
SK330M
SK340M
SK370M
(Fig. 11)
dimensions in bracket are in mm
A single Ø3’’ (76mm) feed pipe should be connected to a single Multi-Steam with a
suitable reduction at the lowest point to allow a ؽ’’ (15mm) condensate drain from the
main steam supply.
SK380M
SK390M
(Fig. 12)
dimensions in bracket are in mm
Two Ø3’’ (76mm) steam outlets to a single Ø5’’ (130mm) feed pipe should be connected
to a single Multi-Steam with a suitable reduction at the lowest point to allow a ؽ’’
(15mm) condensate drain from the main steam supply.
Ø3'’ (76)
ؽ'’ (15)
Min. 7° pipe slope
Min. 4'’ (100)
Insulated pipe
H
Air Duct
Static pressure
+ 2'’ (50)
Min. 2/5 H
min
7°
pipe
slop
e
Ø3'’
(76)
Ø5'’ (130)
Ø2'’ (15)
Min. 7° pipe slope
Static pressure
+ 2'’ (50)
Insulated pipe
Air Duct
Ø3'’
(76)