SK300-XL Steam Humidifier
13
Stage 4 – Water Drain Connection
Water Drain installation should conform to local codes and regulations.
Any installation work must be carried out by suitably qualified personnel.
Water Drain
Specification
Water Drain temperature: 140˚F (+60˚C)
Model
Water Drain Outlet
Connection size
Pan Drain Outlet
Connection size
SK330M
SK340M
SK370M
SK380M
SK390M
3/4’’
(20mm)
1/2’’
(15mm)
Water Drain
Installation
Water drain outlet connection should be connected to drain pipe of sufficient size.
We recommend the use of standard copper hydraulic pipes.
Minimum water drain pipe gradient should be ¼’’ (1.5mm) in 40’’ (1m) horizontal run.
No drain trap is required.
(Fig. 14)
!
SK300-XL
4 ¾’’ (120)
Ø 1½'’ ( 38)
minimum
Ø 3/4’’ (20mm)