SK300-XL Steam Humidifier
1
Safety
ELECTRICITY
All work concerned with electrical installation MUST only be performed by skilled and
qualified technical personnel (e.g. electrician or technician with appropriate training).
The customer is always responsible for ensuring the suitability of the technical
personnel.
Please observe the local regulations concerning the provision of electrical
installations.
HEALTH &
SAFETY
NEP has considered aspects of the design of their humidification systems to reduce
as far as possible the risk of Legionnaires’ disease and other similar conditions but it
is important that users are also aware of their responsibilities.
To prevent the growth of Legionella, users are required to:
Avoid water temperature that favors the growth of Legionella (20-45˚C [68 to
113˚F]).
Avoid
water
stagnation.
Clean and disinfect the humidification system.
Have a competent person carry out a risk assessment of the water system
supplying the humidifier to ensure the water supply is of an acceptable
quality
CORRECT USE
Neptronic® systems and products are designed only for humidification use.
Any other application is not considered use for the intended purpose. The
manufacturer cannot be made liable for any damage resulting from incorrect use.
ACCESS
NEVER LEAVE SK300-XL CABINET KEYS IN THE DOORS AS UNAUTHORIZED
ACCESS TO LIVE ELECTRICAL PARTS MAY BE GAINED – ALWAYS STORE
KEYS CENTRALLY WITH NOMINATED RESPONSIBLE PERSON.
WATER
Neptronic® systems are designed to be used with mains, reverse osmosis,
demineralized or partially softened water. On no account attempt to introduce any
other fluid or chemical into the system without first consulting NEP or its authorized
distributor.
Water supply must not exceed the max pressure of 70 psig (480 kPa), or pressure
limits laid out in the Specification and Installation Instructions, and should comply
with local regulations.