SK300-XL Steam Humidifier
23
Operation display
Description display modes
''OFF'' Mode
When the rocker switch is in the ''OFF'' position, the display shows the model of
the humidifier and the program version number.
(Illus. 52)
Scroll Mode
When the rocker switch is in the auto position, the display scrolls the following information every 6 seconds:
Display Description
Comment
Display Space and Duct Relative
Humidity readings.
Only on modulating humidifiers (suffix M).
If no High limit Duct sensor is installed second line
is left blank
Quantity of steam produced by
the humidifier
I.e.: The actual output of the humidifier at that
moment is 30 lb/hr.
A L A R M
L E V E L
Low water level.
Below this water level, the humidifier shuts off
and the water supply valve is activated until
sufficient level is reached.
C O N T R O L
L E V E L
Water level is controlled
The water supply valve is activated below this
level.
H I G H
L E V E L
Water at maximum level.
The water supply valve is automatically
deactivated.
NEP 3.6
SK390M
RH 25%
DCT 68%
lb /hr
3 0