SK300-XL Steam Humidifier
8
Stage 1 – Unit Positioning and Mounting
General
considerations
Any installation work MUST be carried out by suitably qualified personnel.
The following considerations should be taken into account before deciding on the
location for the SK300-XL Steam Humidifier:
Plan a location easy to access in order to permit an easy inspection and
servicing of the humidifier.
Do not install humidifier where failure of the appliance could cause damage
to the building structure or to costly equipment.
Location area should be well ventilated, ambient temperature should not
exceed 86˚F (30˚C).
Positioning the
Humidifier
The humidifier must be installed to ensure the steam hose length is kept to the
shortest possible length.
For flexible steam hose: the total steam line length should not exceed 16
feet (5 meters). For longer distances use insulated hard piping.
For insulated hard piping: the total steam line length should not exceed 50
feet (15 m). For longer steam line runs, consult factory.
Observe the minimum access distances as shown in figure 5.
(Fig. 5) Standard enclosure
dimensions in bracket are in mm
Minimum
Clearances
Minimum clearances are :
Top: 20’’(510mm) minimum
Electrical panel side: 24’’ (600mm) minimum
Front: 30’’ (800mm) minimum
The humidifier is designed to be installed directly on the floor.
Provide a level, solid foundation for the humidifier.
Ensure that the floor beneath the humidifier is water proof to withstand any water
spillage during servicing or if a problem occurs.
The humidifier is provided with adjustable legs in order to ensure proper level.
!
30'’
[80
0]
min
imu
m
20'’ [510]
minimum
24'’ [60
0]
minimu
m