SKE Steam Humidifier
Installation Instructions and User Manual
11
4.2.
Positionning of S.A.M or S.A.M.E2
4.2.1. Duct mounting
Steam manifold should be mounted and
secured through the side of the air
handling unit or duct. Provision should be
made for safe accessibility, ideally with an
observation light and window.
Check that the construction of the duct
wall is suitable enough to support the
steam pipe for the duration of the
installation life.
Dimension of hole size in the duct must be
as per table below:
Steam manifold Ø
Hole size ØA
35mm
51mm
54mm
78mm
(Illus. 9)
WARNING
: Risk of condensing. Ensure
that the minimum distance of the end of
the manifold is at least 102mm from the
top of the duct.
Minimum distance
(Illus. 10)
4.2.2. Recommendations for SAM distribution pipes
Model
Maximum
Capacity
Outlet
Distribution pipes
Maximum
static
pressure
kg/hr
Qty
Diameter
Minimum
length
Maximum
length
mm
mm
mm
(Pa)
SKE05
5
1
35
300
600
1245
SKE10
10
600
1200
SKE20
20
SKE30
30
2
SKE40
40
SKE50
50
54
800
1600
SKE60
60
SKE80
80
3
Note
: For higher static pressure, please contact the manufacturer.
5'’
(120mm)
5
'’
(1
2
0
m
m
)
ØA
4'’ minimum
(102mm)