SKE Steam Humidifier
Installation Instructions and User Manual
14
5.
Steam output connection
5.1.
Typical installation
(Illus. 21)
5.2.
General recommendations
Please follow these general rules of installation in order to avoid any static pressure inside distribution
pipes and into the humidifier evaporation chamber, and also to avoid any condensation accumulation.
a)
The slope of the steam hose (rigid or flexible)
should not be less than 15%
(7 horizontal length for
1 vertical length) in order to ensure continuous
drainage of condensation back to humidifier or to
steam trap.
b)
Total length of the flexible steam hose should not
exceed 5 meters.
Longer runs will result in added
condensation losses. Whenever possible, use
insulated copper piping. Flexible steam hose should
be used for short runs (up to 5m) or for
interconnecting between the rigid pipes.
c)
Whenever using rigid copper, these ones should
be insulated to diminish condensation build up.
(Illus. 22)
5.3.
Installation of “S” traps on the steam line
The lowest point of any steam hose or rigid pipe must be the humidifier.
If necessary a steam
separator (S trap) should be installed higher than the static pressure of the system by at least 51mm.
(Illus. 23)
(Illus. 24)
1 5 %
2
7
2
4
4
3
3
5
1
1
1
6
H u m id ifie r
Incorrect installation
8"
15%
15%
Use "S" separator
when ceiling space is
limited and you need
to create 15% slopes
Steam outlet
Use ‘’S’’ separator when
the steam distributor is
lower than the humidifier
steam outlet
8'’
(203mm)
15%
1
Clamps
2
Flexible hose
3
Rigid copper pipe
4
Insulation
5
Steam distribution manifold
6
Duct
7
Long radius copper pipe