SKE Steam Humidifier
Installation Instructions and User Manual
17
6.
Plumbing connection
CAUTION:
Water supply installation should conform to local codes and regulations. Any installation work must
be carried out by suitably qualified personnel.
The operation of SKE series humidifier is independent of variable water conditions, with soft or hard water.
Therefore, for normal operation, no pre-treatment of water is necessary.
Bottom view (Illus. 28)
Model
Dimensions (mm)
A
B
C
D
E
SKE05
165
51
232
105
44
SKE10
SKE20
SKE30
SKE40
184
44
248
105
44
SKE50
SKE60
SKE80
179
44
248
105
44
(Illus. 29)
6.1.
Water supply
Water inlet specifications:
Inlet water pressure: 0,7 to 4,8 bars (10 to 70
psig)
Maximum temperature: 30
C maximum
3/8'' (DN10) standard copper water line
connection
A shut off valve (not supplied) should be
installed in the water supply line to the unit,
close to the humidifier to facilitate servicing.
It is recommended to install a standard water
strainer in the water supply line.
It is recommended to install a water hammer
arrestor, in order to absorb hydraulic shock and
minimize water hammer when the fill valve
closes.
Please follow the steps described below:
Connect 15mm water supply pipe to the flexible
hose (supplied).
Finger tighten the swivel top 20mm fitting to the
male threaded part of the valve.
CAUTION
: RISK OF DAMAGE TO THE VALVE. DO
NOT USE WRENCH TO TIGHEN SWIVEL.
(Illus. 30)
A
B
C
D
E
Minimum
500mm
Minimum
200mm
Minimum building sid
e drain of 42mm Ø
SKE Humidifier
22mm Ø
15mm Ø
B a s e p la te o f
h u m id ifie r
M a le th re a d e d p a rt o f
th e v a lv e
F ill v a lv e
(In te rn )
W a te r s u p p ly fle x ib le
h o s e (p /n S P 6 8 4 2 )