SKE Steam Humidifier
Installation Instructions and User Manual
26
9.1.
Description display modes
9.1.1. ''OFF'' Mode
When the rocker switch is in the ''OFF'' position, the
display shows the model of the unit and the program
version number.
(Illus. 52)
9.1.2. Scroll Mode
When the rocker switch is in the auto position, the display scrolls the following information every 6 seconds:
Display
Description
Comment
Display Space and Duct Relative
Humidity readings.
Only
on
modulating
humidifiers
(suffix M). If no High limit Duct
sensor is installed second line is left
blank
)
kg/hr
8
Quantity of steam produced by
the humidifier
I.e.: The actual output of the unit at that
moment is 8 kg/hr
ALARM
LEVEL
Low water level.
Below this water level, the humidifier
shuts off and the water supply valve is
activated until sufficient level is reached.
CONTROL
LEVEL
Water level is controlled
The water supply valve is activated
below this level.
HIGH
LEVEL
Water at maximum level.
The water supply valve is automatically
deactivated
N E P 3 . 3
S K E 1 0 M
RH 25%
DCT 68%