SKE Steam Humidifier
Installation Instructions and User Manual
33
10. Re assembly of the evaporation chamber
Rinse out the container and the cover with water.
Check the cover gasket, and make sure that the gasket is well placed before to re-install the cover on the
container. The water level sensor should be in front of the drain/fill connection of the evaporation chamber.
Tighten the latches around the cover (3,4 or 6).
Replace the evaporation chamber in the humidifier.
Tighten the water drain/fill connection nipple.
Replace the steam hose(s) on the outlet of the evaporation chamber.
Reconnect the connector of the water level sensor, high temperature switch (klixon) and the high voltage
connector of the heating element.
CAUTION
: RISK OF FIRE. MAKE SURE THE HIGH VOLTAGE CONNECTOR IS PROPERLY LOCKED. AN
UNPROPER CONNECTION MAY PROVOKE ELECTRIC ARCS.
11. Start-up of the humidifier
Turn on the main power supply to the humidifier.
The POWER light of the front panel should be illuminated.
Press the
button to enter the programming mode, to reset the Running hours (see section 9.2-
Programming Step 3).
Set the front panel switch ''AUTO/OFF/DRAIN'' to AUTO. The humidifier will command to fill the evaporation
chamber with water; the FILL light should be illuminated.
It is possible that the CHECK light will illuminate because the evaporation chamber is empty. This signal will
extinguish as soon as the normal condition will be reach.
If there is a humidity demand, the humidifier will produce steam again.