SKE Steam Humidifier
Installation Instructions and User Manual
8
Model
Wall Mounting Dimensions
mm
A
B
C
D
E
F
G
SKE05
-
202
165
516
-
-
-
SKE10, SKE20,
SKE30, SKE40
-
254
203
625
276
203
254
SKE50, SKE60,
SKE80
102
305
265
698
276
576
-
3.4.
Weather proof enclosure unit positioning and mounting
20" (51cm)
minimum
24" (60cm)
minimum
42" (107cm)
minimum
24" (60cm)
minimum
(Illus. 4a)
dimensions in bracket are in cm
General
Recommendations
The humidifier should be installed in an easily accessible location to allow proper
access for inspection and servicing of the humidifier. The unit should never be
installed in a location where unusual malfunction of the unit can cause damage to
the building structure or to costly equipment.
Minimum
Clearances
Minimum clearances are :
Top, 51 cm minimum
Both sides, 60 cm minimum
Front, 107 cm minimum
Note: Above minimum clearances are indicated for inspection and servicing
access.
The humidifier is designed to be installed directly on the floor/roof or a curb.
Provide a level, solid foundation for the humidifier.
Ensure that the floor/roof beneath the humidifier is water proof to withstand any
water spillage during servicing or if a problem occurs.
Attach securely and safely the SK enclosure.