SKE Humidifier
User Manual
8
4.2.
Positionning of S.A.M or S.A.M.E2
4.2.1. Duct
mounting
Steam manifold should be mounted and
secured through the side of the air
handling unit or duct. Provision should be
made for safe accessibility, ideally with an
observation light and window.
Check that the construction of the duct
wall is suitable enough to support the
steam pipe for the duration of the
installation life.
Dimension of hole size in the duct must
be as per table below:
Steam manifold Ø
Hole size ØA
35mm 51mm
51mm 78mm
5'’
(120mm)
5'’
(1
2
0
mm)
ØA
(Illus. 9)
WARNING
: Risk of condensing. Ensure
that the minimum distance of the end of
the manifold is at least 102mm from the
top of the duct.
4'’ minimum
(102mm)
Minimum distance
(Illus. 10)
4.2.2.
Recommendations for SAM distribution pipes
Maximum
Capacity
Outlet Distribution
pipes
Diameter
Minimum
length
Maximum
length
Maximum
static
pressure
Model
kg/hr
Qty
mm mm
mm
(Pa)
SKE05
5 300
600
SKE10
10
SKE20
20
1
SKE30
30
600 1200
SKE40
40
35
SKE50
50
SKE60
60
2
SKE80
80 3
51
750 1500
1245
Note
: For higher static pressure, please contact the manufacturer.