SKE Humidifier
User Manual
14
6. Plumbing
connection
The operation of SKE series humidifier is independent of variable water conditions, with soft or hard water.
Therefore, for normal operation, no pre-treatment of water is necessary.
A
B
C
D
E
Bottom view (Illus. 28)
Dimensions (mm)
Model
A B C D E
SKE05
165 51 232 105 44
SKE10
SKE20
SKE30
SKE40
184 44 248 105 44
SKE50
SKE60
SKE80
179 44 248 105 44
Minimum
500mm
Minimum
200mm
Minimum building sid
e drain of 42mm Ø
SKE Humidifier
22mm Ø
15mm Ø
(Illus. 29)
6.1. Water
supply
Water inlet specifications:
Inlet water pressure: 0,7 to 4,8 bars (10 to 70 psig)
Maximum temperature: 30
°
C maximum
3/8'' standard copper water line connection
A shut off valve (not supplied) should be installed in the water supply line to the unit, close to the
humidifier to facilitate servicing.
It is recommended to install a standard water strainer in the water supply line.
Please follow the steps described below:
Connect 3/8'' copper pipe to the bottom 3/8''
compression fitting (supplied).
Finger tighten the swivel top 3/8'' fitting to the
male threaded part of the valve.
CAUTION
: RISK OF DAMAGE TO THE
VALVE. DO NOT USE WRENCH TO TIGHEN
SWIVEL.
Base plate of
hum idifier
M ale threaded part of
the valve
Swivel top
Com pression
fitting
Fitting
supplied
W ater line
3/8'' hydraulic pipe
Fill valve
(Intern)
(Illus. 30)