SKE Humidifier
User Manual
27
12. Service
12.1. General
The humidifier is set to give service demand on the alphanumeric display and on the CHECK light
after is has reached the service hours setting (see section 9.2- Programming)
The routine service is a cleaning of the evaporation chamber.
We recommend setting the service demand depending on the water quality, the frequency of
automatic drain cycles and the demand placed on the humidifier.
The manual cleaning frequency can be from every 2 months to once a year.
12.2. Evaporation chamber cleaning
WARNING
: RISK OF BURN. THE EVAPORATION CHAMBER AND ITS CONTENT CAN BE
EXTREMELY HOT, CHECK TEMPERATURE BEFORE HANDLING.
1. Cool down evaporation chamber
Set the front panel switch ''AUTO/OFF/DRAIN'' to DRAIN. The humidifier will command a drain cycle.
Ensure that the evaporation chamber is completely empty. When it is empty, set the front panel switch
''AUTO/OFF/DRAIN'' to AUTO, the evaporation chamber will be fill with cool water; the FILL light will be
illuminated.
As soon as the evaporation chamber is full of cool water, the FILL light will extinguish, Set the front panel
switch ''AUTO/OFF/DRAIN'' to DRAIN again.
At the end of this drain cycle, check the temperature of the evaporation chamber, to do so, open the front
door of the humidifier and touch the evaporation chamber with the back of your hand, If it is cool enough you
can go the sequence #2 if not repeat the cool down operation until it will be cool enough.
Set the front panel switch ''AUTO/OFF/DRAIN'' to OFF
2. Shut down of the electrical supply
CAUTION
: RISK OF ELECTRIC SHOCK. SHUT DOWN THE ELECTRIC SUPPLY OF THE
HUMIDIFIER
Turn off the main power supply to the humidifier.
3. Disconnection of heating element(s)
Remove the high voltage connector located at the top right hand side of the mechanical compartment.
o
Model SKE05: Unscrew the connector.
o
Model SKE10 to SKE80: squeeze the locking ears of the high voltage connector and pull it apart.
4. Disconnection of the other accessories.
Disconnect the connector from the water level sensor; this connector is attached to a cable that enters the
mechanical compartment just below the high voltage connector. Squeeze the locking ear of the connector
and pull it apart.
Remove the connection to the high limit sensor (klixon), located on the top cover of the evaporation
chamber.
5. Disconnection of steam hose and water pipe
Remove the steam hose(s) at the top of the evaporation chamber.
Remove the water drain/fill connection to the evaporation chamber. To do this, unscrew the nipple located
on the lower right hand side of the evaporation chamber.
6. Removing the evaporation chamber
The evaporation chamber may now be freely removed from the humidifier cabinet.
CAUTION
: The evaporation chamber still contains 1 inch of water, ensure that you do not reverse this water
on yourself.
Make sure that your footing is secure when lifting out the evaporation chamber. On large humidifier (SKE50
to SKE80) it may weigh more than 15 kg. This operation may require another person to assist you in
removing the evaporation chamber.
7. Opening of the evaporation chamber
Remove the cover from the evaporation chamber.
o
Model SKE05: Unlatch the 3 latches located around the evaporation chamber,
caution: these latches
are very tight, we recommend you to help you with a screwdriver or pliers to do
this.
o
Model SKE10 to SKE80: Turn the latches of the 4 or 8 latches located around the evaporation
chamber.
Remove the cover from the evaporation chamber.