1.1.3. Options 

avalaible 

The following options are available when purchasing a SKE humidifier: 
 

 

Modulating control humidifier – suffix M (i.e. SKE20

M

 

Humidifier for system supplied with Deionised water or Reverse Osmosis water, 
dissolved solids more than 1 ppm (SF DI-APPLICATION) 

 

Humidifier for system supplied with Deionised water or Reverse Osmosis water, 
dissolved solids more than 0.028 ppm (SF ULTRAPURE-DI) 

 

Space Distribution Unit mounted on humidifier (SDU) or remote installation (SDU-REM) 

 

Network communication system, BACnet – suffix B (i.e. SKE20M-400-3

B

 

Stainless steel humidifier cabinet – suffix P (i.e. SKE20M-400-3

P

 

Dry contact to activate an external fan relay on a call for humidity (SF SK300FANRELAY) 

 
 

1.2. Definition 

1.2.1. Evaporation 

chamber 

Assembly including the metal cylinder and a cover equipped with one or several heater elements. 
It is the heart of the humidifier, which produce steam. 

1.2.2. 

SDU (Space Distribution Unit) 

Integrated steam distribution unit, optional on certain humidifiers. 

1.2.3. Multi-Steam 

system 

Custom made system of steam distribution. This system is designed to allow very short 
absorption distances (less than 900mm). 

1.2.4. 

S.A.M. (Steam Absorption Manifold) 

Steam manifold adapted to air duct size to allow steam absorption in relatively short distance 
(less than 1500mm). 

1.2.5. 

S.A.M.E2 (Steam Absorption Manifold with 2 Eyelets) 

Steam manifold with two eyelets adapted to application with restricted air duct dimensions to 
allow steam absorption in relatively short distance (less than 1500mm). 

 

Summary of Contents for SKE

Page 1: ...SKE ENG 110221 doc Steam Humidifier SKE series HUMIDITY 45 RH Installation instruction user manual READ AND SAVE THESE INSTRUCTIONS...

Page 2: ...oducts Ltd Manufacturer Presentation National Environmental Products Ltd NEP is the owner of the brand Neptronic NEP develops manufactures and services a complete line of Steam humidifiers Humidistat...

Page 3: ...n of humidifier with Space Distribution Unit SDU 13 6 Plumbing connection 14 6 1 Water supply 14 6 2 Drain connection 15 7 Power supply connections 15 8 Low voltage control connections 16 8 1 ON OFF H...

Page 4: ...male cmpression fitting hydraulic for the drain output of the evaporation chamber 1 female compression fitting hydraulic for the drain output of the drip pan 1 female fitting for the water supply conn...

Page 5: ...xternal fan relay on a call for humidity SF SK300FANRELAY 1 2 Definition 1 2 1 Evaporation chamber Assembly including the metal cylinder and a cover equipped with one or several heater elements It is...

Page 6: ...SKE20 20 15 22 1 35 Medium 724 533 318 165 890 SDU 2 SKE30 30 22 33 2 35 Medium 724 533 318 324 1048 SDU 3 SKE40 40 30 44 2 35 Medium 724 533 318 324 1048 SDU 3 SKE50 50 36 53 2 54 Large 794 813 318...

Page 7: ...se the keyholes located on the back panel of the humidifier Before to proceed to the wall mounting take off the Evaporation chamber sub assembly see section 12 Servicing Check the solidity of the chos...

Page 8: ...solution for any particular application 4 1 1 S A M steam absorption manifold Horizontal duct air Illus 5 The SAM is to be installed where absorption distances are short less than 1500mm and or low d...

Page 9: ...an efficient solution 4 1 4 Multi Steam system air Illus 8 The Multi Steam system is to be installed in critical locations in air handling systems particularly where absorption distances are very shor...

Page 10: ...duct must be as per table below Steam manifold Hole size A 35mm 51mm 51mm 78mm 5 120mm 5 120mm A Illus 9 WARNING Risk of condensing Ensure that the minimum distance of the end of the manifold is at le...

Page 11: ...1 air H 10 minimum 250mm 3 minimum 80mm 8 200mm 6 minimum 150mm 2 pipes Illus 12 51mm diameter pipe H 24 minimum 600mm 1 5 H 2 5 H 8 200mm air 2 pipes Illus 13 H 36 minimum 900mm 1 6 H 1 2 H 1 3 H 10...

Page 12: ...D view Illus 15 air 45 air 45 S A M S A M E2 Illus 16 35mm diameter pipe W 10 minimum 250mm 1 2 W 1 pipe Illus 17 W 24 minimum 600mm 1 2 W 1 4 W 1 4 W 2 pipes Illus 18 51mm diameter pipe W 24 minimum...

Page 13: ...condensation losses Whenever possible use insulated copper piping Flexible steam hose should be used for short runs up to 5m or for interconnecting between the rigid pipe runs c Whenever using rigid c...

Page 14: ...t I J SKE05 110 122 Medium Cabinet K L M SKE10 SKE20 102 143 SKE30 SKE40 134 102 143 Large Cabinet N O P Q SKE50 SKE60 SKE80 179 179 132 144 I J L M Small Cabinet SKE05 Medium Cabinet SKE10 20 Medium...

Page 15: ...from the humidifier remote SDU Please follow the piping recommendations section 5 2 Mount the SDU to the wall on brackets not supplied do not drill mounting holes thru the cabinet of the SDU Connect...

Page 16: ...sure 0 7 to 4 8 bars 10 to 70 psig Maximum temperature 30 C maximum 3 8 standard copper water line connection A shut off valve not supplied should be installed in the water supply line to the unit clo...

Page 17: ...block designated L1 L2 and L3 with Low voltage terminal block designated 1 2 and 3 The wiring to the Humidifier should be done by a qualified electrician and conforming to the procedure regulation and...

Page 18: ...ection to the Humidifier control terminal block Connection to HRO20 humidistat or HRO20 with remote humidity sensor SHR10 or SHC80 humidistat 24 VAC Pressure Differential switch High limit 1 4 3 2 F 8...

Page 19: ...stem with humidity controlled by humidifier using SHC80 as Hi limit duct sensor and SHR10 or SHC80 as space sensor 1 8 7 5 4 3 2 F 6 9 SKE To Term 3 To Term F To Term 4 1 3 2 COMMON 0 10 VDC OUTPUT 24...

Page 20: ...0V 4 20mA 0 10V 2 10V Illus 40 Humidity signal 2 10 Vdc 1 8 7 5 4 3 2 F 6 9 2 10 Vcc Pressure Differential Switch High limit Humidistat 5 Vdc Illus 38 PCB970819 REV C Jumper on 2 10V Extra jumper TOP...

Page 21: ...mA 0 10V 2 10V Illus 46 Control signal 2 10 Vdc 1 8 7 5 4 3 2 F 6 9 2 10 Vcc Pressure Differential Switch High limit Humidistat 5 Vdc Illus 44 PCB970819 REV C Jumper on 2 10V Extra jumper TOP PCB MODU...

Page 22: ...operation of the overall system The return duct humidistat must always be located before any outside air intake in order to ensure accurate sensing of the air from the humidified space Alternatively a...

Page 23: ...FILL indicator O Indication that the water supply fill valve is open O Indication that the water supply fill valve is closed 6 STEAM indicator O ON OFF model the STEAM indicator lights when the contac...

Page 24: ...t Relative Humidity readings Only on modulating humidifiers suffix M If no High limit Duct sensor is installed second line is left blank k g h r 8 Quantity of steam produced by the humidifier I e The...

Page 25: ...R H E A T E D Overheated The temperature inside the container has exceeded the boiling temperature The humidifier has automatically shut off P R O B E D E F E C T E D Defected probe The water level s...

Page 26: ...he VAV Set point value desired by using buttons on control panel Note This Step will appear only if Internal has been selected at step 01 03 optional PROPBAND 3 Prop Band allows the set up of proporti...

Page 27: ...tes that the water supply valve is feeding water o DRAIN indicates the drain valve empties the container o CONT indicates that power is supplied to the elements and the unit is producing steam TEST bu...

Page 28: ...button located on the main pc Board This pc Board is located in the electrical compartment 6 This will start up a pre programmed start up cycle This start up cycle will test functions of the humidifie...

Page 29: ...main power supply to the humidifier 3 Disconnection of heating element s Remove the high voltage connector located at the top right hand side of the mechanical compartment o Model SKE05 Unscrew the co...

Page 30: ...Proceed as per the cleaning of the container step 8 Removing and cleaning of the water level sensor A chamber protects the water level sensor Cleaning of the sensor requires removing this chamber o U...

Page 31: ...on and the high voltage connector of the heating element CAUTION RISK OF FIRE MAKE SURE THE HIGH VOLTAGE CONNECTOR IS PROPERLY LOCKED AN UNPROPER CONNECTION MAY PROVOKE ELECTRIC ARCS 11 Start up of th...

Page 32: ...view Bill of Material 13 1 Exploded view A B A B C C D D E E F F G G H I I J J N O P Q R T U V W X Y Steam Trap Assem bly Plastic gril SDU Cabinet Evaporation cham ber base SKE10 to SKE80 Evaporation...

Page 33: ...FOAMLG ASSY SKE05 SW PROBSM ASSY SKE10 20 SW PROBMD ASSY J Water level sensor SKE30 40 50 60 80 SW PROBLAR ASSY SP 6003 K Water supply valve SKE05 to SKE80 SP 6007 IDC SKE05 SW TRAPSMA P SKE10 to SKE...

Page 34: ...400V 3 400V 3 400V 3 D Heater element SE 5937 SE 5980 SE 5983 SE 5981 SE 5982 SE 5983 SE 5955 SE 5984 SE 5983 SE 5955 R Transformer SP 3365 SP 3374 SP 3365 SP 3374 SP 3374 SP 3374 S Contactor SP 3080...

Page 35: ...an operation Check the operation of the high limit humidistat Verify the connections of the wires to the control terminal blocks Power On Check Off Fill Off Steam Off Humidifier does not produce steam...

Page 36: ...ction of the brown wire to the Main pc board Power On Check On Fill Off Steam Off Humidifier is not operating and the CHECK light is ON Drain Off PROBE DEFECTED The water level sensor is damaged Repla...