SKE Humidifier
User Manual
5
3. Mechanical
installation
3.1. General
recommendations
CAUTION
: RISK OF ELECTRIC SHOCK. DISCONNECT THE APPLIANCE FROM THE ELECTRIC
SUPPLY BEFORE TO PROCEED TO INSTALLATION.
Location: Plan a location easy to access in order to permit an easy inspection and servicing of the
humidifier.
Do not install humidifier where failure of the appliance could cause damage to the building structure or to
costly
equipment.
This location should be well ventilated; the ambient temperature should not exceed 30
°
C.
The maximum distance between the humidifier and the ventilation duct should not exceed 5 meter
(maximum length of the steam hose).
(0,60 m)
(0,25 m)
(1 to 1,2 m)
10'’
24'’
39 to 48'’
E
neptronic
Positioning
(Illus. 3)
3.2. Positioning
The front panel and the right side (electrical compartment)
should be accessible in order to permit the servicing.
Leave a clearance of at least 1,25m to the front panel and
0,6m to the right side.
The humidifier should be mounted at a minimum of 1m to
1,2m above floor level.
Leave a clearance of at least 0,25m under the humidifier for
installation of water supply, drain piping and electrical
connections.
3.3. Wall
mounting
Use the keyholes located on the back panel of the humidifier.
Before to proceed to the wall mounting, take off the
Evaporation chamber sub assembly (see section 12,
Servicing).
Check the solidity of the chosen support or wall (bricks,
concrete, stud partition wall, etc) on which the humidifier will
be mounted.
Drill holes for the upper anchors (holes with eyelet) into the
support or wall as per dimensions specified in the table
(illus.4).
The holes dimensions (diameter and depth) should by in
accordance with the recommendations of the chosen anchors.
Install then bolt anchors, if required.
Screw-on the 2 or 3 upper screws (holes with eyelet) of a
minimum diameter of #10 (6mm) (screws are not supplied).
Leave a clearance between head screws and wall in order to
permit the mounting of the humidifier.
Use the keyholes located on the back panel of the humidifier.
Hang on the humidifier to the 2 or 3 screws; it is preferable let
the front door open during this operation.
According to the size and weight of the humidifier, you may
need the help of a second person to assist you.
When the humidifier is positioned on the upper screws, tighten
the screws to secure the humidifier.
If applicable, install and secure lower screws.
Front view
(Illus. 4)
Dimensions
mm
Model
A B C D E F G
SKE05
- 202 165 516 -
-
-
SKE10, SKE20,
SKE30, SKE40
- 254 203 625 276 203 254
SKE50, SKE60,
SKE80
102 305 265 698 276 576 -