SKE Humidifier
User Manual
6
4.
Steam dispersion system selection and positioning
4.1. Steam
dispersion system selection
In order to prevent the accumulation of condensation in air ducts, NEP has designed 4 basic
configurations of steam distribution to provide the client with the most economical solution for any
particular application.
4.1.1.
S.A.M. (steam absorption manifold) Horizontal duct
air
(Illus. 5)
The SAM is to be installed
where absorption distances
are short, less than 1500mm,
and/or low duct temperatures
are in effect.
4.1.2.
S.A.M.E2 (steam absorption manifold) Horizontal duct
90
0
air
(Illus. 6)
The SAME2 is to be installed
where absorption distances are
short, less than 1500mm and/or
low duct temperatures are in
effect. SAME2 are used in
applications with restricted duct
dimensions.