SKE BACnet Steam Humidifier
Installation Instructions and User Manual
4
1.2.
Definition
1.2.1. Evaporation chamber
Assembly including the metal cylinder and a cover equipped with one or several heater elements.
It is the heart of the humidifier, which produce steam.
1.2.2. SDU (Space Distribution Unit)
Integrated steam distribution unit, optional on certain humidifiers.
1.2.3. Multi-Steam system
Custom made system of steam distribution. This system is designed to allow very short
absorption distances (less than 900mm).
1.2.4. S.A.M. (Steam Absorption Manifold)
Steam manifold adapted to air duct size to allow steam absorption in relatively short distance
(less than 1500mm).
1.2.5. S.A.M.E2 (Steam Absorption Manifold with 2 Eyelets)
Steam manifold with two eyelets adapted to application with restricted air duct dimensions to
allow steam absorption in relatively short distance (less than 1500mm).
1.3.
Output and Power Consumption
Model
Steam
Consumption
Output
Capacity
(Kg/Hr)
Power
(KW)
Current (A)
Qty
Diam
(mm)
230V
1 phase
400 V
3 Phases
SKE05
5
3,7
16
5,5
1
35
SKE10
10
7,5
33
11
1
35
SKE20
20
15
-
22
1
35
SKE30
30
22
-
33
2
35
SKE40
40
30
-
44
2
35
SKE50
50
36
-
53
2
54
SKE60
60
44
-
64
2
54
SKE80
80
60
-
87
3
54