SKE-XL BACnet Steam Humidifier
Installation Instructions and User Manual
12
Stage 2
– Steam Distribution Installation
Steam Pipe Work To Duct Connections
SKE90&100
(llus. 11)
A single Ø76mm feed pipe must be connected to a single Multi-Steam with a suitable
reduction at the lowest point to allow a Ø15mm condensate drain from the main steam
supply.
SKE110&120
(Illus. 12)
Two Ø76mm steam outlets to a single Ø130mm feed pipe must be connected to a single
Multi-Steam with a suitable reduction at the lowest point to allow a Ø15mm condensate
drain from the main steam supply.
Min. 7° pipe slope
Insulated pipe
H
Air
Duct
Static pressure
Min. 2/5 H
Ø76 mm
Ø15 mm
Min 100 mm
+ 50 mm
min
7°
pipe
slop
e
Ø76mm
Ø130 mm
Ø15 mm
Min. 7° pipe
slope
Static pressure
+ 50 mm
Insulated
pipe
Air
Duct
Ø76mm