SKE-XL BACnet Steam Humidifier 

Installation Instructions and User Manual

 

 

21 

Initial Verification & Start-up 

 

Initial verification and start-up 

– commissioning – must be carried out by suitable 

qualified personnel. 

Clearance 

1.  Ensure  that  the  humidifier  cabinet  is  installed  in  a  location  where  the 

humidifier can be serviced correctly. 

 

Electrical 

2.  Check that the power supply (voltage) conforms to the appliance name plate 

on the humidifier side. 

 

3.  Confirm that 24Vac is present between tab  1&2 of Control terminal, located 

on  the  control  connection  PCB.  Remove  the  front  top  cover  to  get  to  this 
PCB. 

 

Water 

4.  Ensure that water is supplied to the humidifier. A shut-off valve must be 

placed outside the humidifier.  
Once the water shut-off valve is turned ON, ensure that there are no 
apparent leaks.  

 

5.  Confirm  that  Drain  piping  is  properly  connected  with  a  pitch  of  least  6.5mm 

per 300mm horizontal run. 

 

Steam 

6.  Check that steam distributors are properly installed into the ventilation duct. 

 

7.  Verify that the flexible steam hoses and rigid steam supply pipes are shorter 

length  than  5m  in  total  and  properly  sloped  and  have  condensation  S  traps 
wherever required. 

 

Controls 

8.  Ensure  that  an  air  flow  switch  is  installed  and  properly  connected  to  the 

humidifier. 

9.  Ensure  that  a  High  limit  duct  humidistat  is  installed,  properly  connected  to 

the humidifier and set point is properly adjusted (recommended value: 80%). 

 

 
 

 

10.  Verify  that  a  Room  humidistat  or  returned  air  duct  humidistat  is  installed, 

properly connected to the humidifier and set point is properly adjusted. 

 

11.  Turn Power ON at the disconnect switch. 

 

12.  Confirm the control signal is matching control signal jumper on Main PCB. 

 

Start-up 

13. 

Proceed to start-up the Humidifier, as follows:

 

 

a)  Open the front access door of the humidifier cabinet; make sure that manual drain 

valve is closed. 

 

b)  Verify that there is a humidity demand. 

Humidity demand is displayed on the humidifier LCD screen. 

 

c)  Start  up  the  humidifier  by  putting  rocker  switch  located  on  the  humidifier  control 

panel at  the ON position  

 

d)  Water will start to flow in and slowly rise in the water level sight glass located on 

the side of the evaporation chamber. 
Observe for water leak along the water line. 

 

e)  Humidifier LCD screen will display the water level with 3 levels of information: 

Alarm level / Control level / High level  

 

f) 

As soon as Control level is reached, contact will be activated and heater elements 
powered. 
From a cold start steam will be produced 3 to 5 minutes after contactors closing 

 

g)  Observe for water and steam leaks. 

 

Safety Test 

14.  Check the location of the air flow switch in the system and its operation by stopping the 

fan. 
With no air movement in the air duct, the humidifier will automatically stop. 

 

Drain and Reset 

15.  Turn the humidifier OFF, by putting rocker switch of the control panel to the 0 (middle) 

position  

 

16.  Execute a manual drain, by putting rocker switch of the control panel to the Drain 

position 
A water jet directed on the water level sensor located in the water level sight glass will 
start and create bubbles around it. 

 

17.  Reset Air flow switch and humidistat(s) to the proper value, if needed. 

 

End 

18.  Humidifier is ready for normal operation. 

 

!

Summary of Contents for SKE100

Page 1: ...Electric Steam Humidifier SKE90 100 110 120 Series SKE XL BACnet INSTALLATION INSTRUCTIONS Read and save these instructions SKE XL BACnet IOM Rev 180206...

Page 2: ...ion Clean and disinfect the humidification system Have a competent person carry out a risk assessment of the water system supplying the humidifier to ensure the water supply is of an acceptable qualit...

Page 3: ...ity of your installation and operation as per the manufacturer s recommendations The application of these instructions is one of the conditions for the application of the warranty The application of t...

Page 4: ...ting 9 Stage 2 Steam Distribution Installation 10 Stage 3 Water Supply Installation 13 Stage 4 Water Drain Connection 14 Stage 5 Electrical Supply and Installation 15 Stage 6 Electrical Control Connec...

Page 5: ...odel Steam cap kg h Power kW Current A Nb of outlets Multi Steam header diam mm 400V 3ph SKE90 90 66 96 1 76 mm SKE100 100 74 107 1 76 mm SKE110 110 82 119 2 76 mm SKE120 120 90 130 2 76 mm Notes Maxi...

Page 6: ...ons in mm Steam Outlet Diam D E Drain Outlet Diam Water Inlet Diam F G SKE90 SKE100 1 76 462 n a 20 15 383 190 SKE110 SKE120 2 76 462 230 20 15 383 190 Note Drain outlet and water supply inlet are loc...

Page 7: ...Model No of Steam Outlets Dimensions in mm Steam Outlet Diam D E Drain Outlet Diam Water Inlet Diam F G SKE90 SKE100 1 76 109 1291 20 15 NPT 383 190 SKE110 SKE120 1 100 109 1291 20 15 NPT 383 190 Note...

Page 8: ...tem dry weights Handling and Lifting The SKE XL Steam Humidifier MUST always be handled and lifted with care and must remain in its original packaging for as long as possible prior to installation The...

Page 9: ...nicians with appropriate training The customer is responsible for ensuring their suitability To install the SKE XL Steam Humidifier and its associated components no special tooling is required above t...

Page 10: ...ensure the steam hose length is kept to the shortest possible length For flexible steam hose the total steam line length must not exceed 5 meters For longer distances use insulated hard piping For in...

Page 11: ...se must not exceed 5 m or insulated rigid piping must not exceed 15 m 5 Whenever possible use rigid copper piping flexible steam hose can be used for short runs or for interconnecting between rigid pi...

Page 12: ...l size Multi Steam units so that they can be placed side by side 3 For installation of Multi Steam units please refer to Neptronic Multi Steam Installation Instructions Horizontal duct Illus 9 Vertica...

Page 13: ...to allow a 15mm condensate drain from the main steam supply SKE110 120 Illus 12 Two 76mm steam outlets to a single 130mm feed pipe must be connected to a single Multi Steam with a suitable reduction...

Page 14: ...er Maximum water supply pressure 70 to 480kPa Minimum water temperature 4 C Maximum water temperature 40 C Model Water inlet Connection size SKE90 SKE100 SKE110 SKE120 15 mm Water Supply Line Installa...

Page 15: ...nected to drain pipe of sufficient size We recommend the use of 20mm minimum standard copper hydraulic pipes Minimum water drain pipe gradient must be 6 5mm per 300mm horizontal run No drain trap is r...

Page 16: ...technicians with appropriate training Please observe local codes and regulations concerning the provision of electrical installations WARNING Risk of electric Shock Ensure that the electrical supply i...

Page 17: ...RO humidity controller Illus 16 Note If interlock is not used a jumper must be installed between terminals F 5 Control Signal The selection of the control signal is made through the menu Wire the cont...

Page 18: ...trol Connections Humidifier Control with Humidity Sensors Neptronic SKE XL Steam Humidifier can be installed in conjunction with Neptronic SHR10 or SHC80 humidity sensors Illus 18 1 8 7 5 4 3 2 F 6 9...

Page 19: ...by Neptronic SHR10 or SHC80 room or duct humidity controller Illus 19 Dry Contacts 2 volt free contacts are provided Operation fan contacts One normally connected to common and one normally open cont...

Page 20: ...n be used The room humidistat must be located on an inside wall or column It must not be near any discharge air from supply ducts or sources of heat or cold The airflow switch must be positioned to ac...

Page 21: ...al factory set up ON Mode Configuration DS1 2 3 Baud rate selection Baud rate Switch 2 Switch 3 9600 OFF OFF 19200 ON OFF 38400 OFF ON 76800 factory set up ON ON B DS1 JP2 A TB1 DS2 JP3 O N 1 2 3 4 5...

Page 22: ...nected to the humidifier and set point is properly adjusted 11 Turn Power ON at the disconnect switch 12 Confirm the control signal is matching control signal jumper on Main PCB Start up 13 Proceed to...

Page 23: ...rviced To stop the CHECK indicator from flashing after servicing see Step 03 in the Programming Mode section O No abnormal conditions of operation 5 FILL indicator O Indication that the water supply f...

Page 24: ...ptimum water level in evaporation chamber Water temperature in Celsius Water temperature inside the evaporation chamber List of Alarms When the following conditions occur the diagnostic messages overr...

Page 25: ...shut off Klixon open Temperature in the evaporation chamber exceeded the preset temperature of the high temperature switch PCB Fuse open Internal 24vac is shorted 24 VAC Shorted External 24vac for hu...

Page 26: ...ative humidity set point Duct Source External only Percentage From 10 to 90 02 Setting of automatic drain cycle of evaporation chamber Note In general harder the water is more often the drain cycle mu...

Page 27: ...ustment Range from 4 to 16 min 07 User adjustment Delay to drain out the humidifier from its remains water when there is no demand in order to prevent bacteria growth Range from 1 to 250 Hrs Default 7...

Page 28: ...1 DRAW N BY P C SK3XLB BACNET REV 1 6 W iring diagram SK 300 XL BACNET 3 phases National Environmental Products LTD 400 Boul Lebeau St Laurent Qu bec Canada H4N1R6 Tel 514 333 1433 Fax 514 333 3163 JP...

Page 29: ...SKE XL BACnet Steam Humidifier Installation Instructions and User Manual 28 Exploded View Illus 25 A C D B E Z K N O J T Control panel H I L...

Page 30: ...ub assembly All models SW GWATLEV SUB K Water supply valve All models SP 6007 L Water temperature sensor All models SW GWATTEMP ASSY N SKE LCD display All models NW SK300BDISPLAY O On Off Drain switch...

Page 31: ...u blvd Montreal Qc H4N 1R6 Canada www neptronic com Toll free in North America 1 800 361 2308 Tel 514 333 1433 Fax 514 333 3163 Customer service fax 514 333 1091 Monday to Friday 8 00am to 5 00pm East...

Reviews: