SKE-XL BACnet Steam Humidifier
Installation Instructions and User Manual
23
Operation Display
Description Display Modes
''OFF'' Mode
When the rocker switch is in the ''OFF'' position, the display shows the model of
the humidifier and the program version number.
(Illus. 24)
Scroll Mode
When the rocker switch is in the auto position, the display scrolls the following information every 6 seconds:
Display
Description
Comment
Percent of relative humidity
Only on modulating units (suffix M).
Percent of demand
Control signal input response from
0-100%
Percent of output of the humidifier
Capacity output of the humidifier.
Water level in percent to the objective
100% correspond to optimum water level in
evaporation chamber.
Water temperature in Celsius
Water temperature inside the evaporation
chamber.
List of Alarms
When the following conditions occur, the diagnostic messages override the scrolling information:
Display
Description
Comment
Air flow proof
The airflow is not detected by the air pressure switch
(modulating unit only).
Hi limit cut out
Humidity level has exceeded the set point on the high limit
humidistat.
DRAIN
CYCLE
Drain cycle
The unit is in the automatic drain mode
OVER
HEATED
Overheated
The temperature inside the container has exceeded the
boiling temperature. The humidifier has automatically shut
off.
PROBE
DEFECTED
Defective probe
The water level sensor is not operational. The humidifier has
automatically shut off
NEP 3.6
SK390M
HUMIDITY
45.2%
DEMAND
92%
OUTPUT
100%
WATR LVL
92%
WATR TMP
65C
AIR FLOW
OPEN
HI LIMIT
CUT-OUT