SKE-XL BACnet Steam Humidifier
Installation Instructions and User Manual
26
08
Humidity signal input selection.
0-10VDC, 2-10VDC,
0-20mA or 4-20mA
Default : 2-10VDC
09
Duct Humidity signal input selection.
0-10VDC, 2-10VDC,
0-20mA or 4-20mA
Default : 2-10VDC
10
SKB 3XX
NEP r1. 5
Revision level of the program installed
N/A
Note:
1. Any changes made in the Program Mode are saved into a non-volatile memory.
User Adjustment & Diagnostic Menu
To enter to User adjustment & Diagnostic menu: press and hold
(down) and then press
(menu).
Seq
#
Display
Type
Description
Value
01
Reading
SSR Temperature reading
N/A
02
User
adjustment
Water temperature offset user adjustment
Range: from -
10˚C to +10˚C
Default:
0
03
Reading
Water level frequency reading
N/A
04
User
adjustment
Water level offset user adjustment
Range: from -10% to +10%
Default:
0%
05
Reading
Foaming probe value reading
N/A
06
User
adjustment
Drain time user adjustment
Range: from 4 to 16 min
07
User
adjustment
Delay to drain out the humidifier from its
remains water when there is no demand, in
order to prevent bacteria growth
Range: from 1 to 250 Hrs
Default:
72Hrs
08
User
adjustment
Holding temperature of the evaporation
chamber for fast response to demand
Range: from 15 to 90˚C or OFF
Default:
OFF
09
User
adjustment
Anti-freezing temperature for the
evaporation chamber for humidifier to be
installed in weather proof enclosure.
Range: from
4 to 10˚C or OFF
Default:
OFF
10
User
adjustment
Alarm beep, to be selected ON or OFF
Range: ON or OFF
Default:
OFF
11
User
adjustment
Temperature unit scale Celsius or
Fahrenheit
Range: Celsius or
Fahrenheit
Default:
Celsius
12
User
adjustment
LCD Display contrast level
Range: from 0 to 40
Default:
25
(legible LCD)
13
Reading
Model of humidifier and revision number of
program installed.
N/A
HUM. INP
2-10 VDC
D U C T I N P
2 - 1 0 V D C
SSR TmP
40 C
WTR TOFF
100 C
WTR FREQ
8000 Hz
WTR LOFF
100 %
FOAM PRB
207
Drn Tm Out
5 min
No Demnd
72 HRS
Hold Tmp
OFF
Anti-Frz
OFF
ALARM
Beep ON
T Unit
CELSIUS
CONTRAST
25
SKB 3xx
NEP r1.5