SKE4-E Steam Humidifier
Installation Instructions and User Manual
Page | - 17 -
Positioning and Mounting - Weather Proof
Enclosure Unit
Use 8 bolts and washers (not supplied) to
secure the humidifier to the floor/roof.
12" (30 cm)
minimum
20" (51cm)
minimum
42" (107cm)
minimum
12" (30 cm)
minimum
Illustration 12 - Weather Proof Enclosure Positioning
General Recommendations
x
Plan a location that is easy to access and permits an easy inspection and servicing of the
humidifier.
x
Do not install the humidifier where failure of the appliance could cause damage to the
building structure or to other expensive equipment.
x
Maintain the following minimum clearances while installing to enable access for
inspection and servicing.
Side
Minimum Clearance
Top
51 cm
Both sides 30 cm
Front
107 cm
x
The humidifier is designed to be installed directly on the floor/roof or a curb.
x
Provide a level, solid foundation for the humidifier.
x
Ensure that the floor/roof beneath the humidifier is water proof to withstand any water
spillage during servicing or if a problem occurs.
x
Attach the SKE4 enclosure securely and safely, by securing the base plate to the ground
with the use of 8 bolts and washers (not supplied), as per the sizes indicated in the
following table.
Model
Bolt Diameter
SKE4-E05 to SKE4-E80
8mm
SKE4-E90 to SKE4-E120
12mm