SKE4-E Steam Humidifier
Installation Instructions and User Manual
Page | - 24 -
S Trap Installation on the Steam Line
x
The lowest point of any steam hose or rigid pipe must be the humidifier. If the humidifier
cannot be the lowest point of the piping, install one or more steam traps (S Type) at the
lowest point(s) of the steam supply piping. The steam separator (S trap) must be installed
higher than the static pressure of the system by at least 51mm.
Illustration 24 - Steam Output Connection: Incorrect Installation
Illustration 25 - Steam Separator (S trap) Installation
U e S e a a
he
the steam distributor is
lower than the humidifier
steam outlet
8
(203mm)
15%
Minimum 12
(305mm)
Connect to open drain
15%
15%
Use "S" separator
when ceiling space is
limited and you need
to create 15% slopes
Steam outlet
8"
(203mm)
Connect to open drain
Minimum 12
(305mm)