SKE4-E Steam Humidifier
Installation Instructions and User Manual
Page | - 63 -
Stage 2 - Shut Down the Electrical Supply
CAUTION: Risk of electric shock. The electric supply of the humidifier must be
shut down. Disconnect the power at the External Breaker/Fused Disconnect
before commencing servicing.
Once the evaporation chamber is sufficiently cool, remove the power supply to the humidifier at the
disconnect switch or the breaker.
Stage 3 - Remove Additional Water Residue
1. Remove the plumbing compartment access panel and turn on the manual drain valve, in
order to remove any water residue remaining in the silicone piping.
2. Uncouple the clamp connectors to let the evaporation chamber hang down, in order to
remove additional water.
3. Once the additional water has stopped flowing down the evaporation chamber, recouple the
clamp connectors to reconnect the chamber.