background image

 

SKE4-N Steam Humidifier 

Remote SDU Installation Guide 

 

www.neptronic.com

 

Page | 6 

 

Electrical Installation 

 

CAUTION: Risk of electric shock. Disconnect the SDU from the electric supply before proceeding 
with the connection.

 

 

The wiring to the SDU must be done by a qualified electrician and must conform to the procedure, regulation 
and local codes. 

 

Use copper conductors only. 

 

An external over current protection must be installed on the supply, adjacent to the SDU. It is also 
recommended to install a circuit breaker. 

 

To provide strain relief to the supply cable, install a knock-out (not supplied) at the bottom of the SDU. 

 

Ensure that the size of the wire conductors is appropriate for the current supplied. 

 

Ensure that each terminal connection is properly secured. 

 

Ensure that the ground conductor is equipped with a ring terminal and is connected directly to the electrical 
panel. 

 

Table 3 - SDU Power Supply Specifications 

Model 

SDU 

Amperage (A) 

120V/1ph 

208V/1ph 

240V/1ph 

480V/1ph 

600V/1ph 

SKE4-N02 

SDU4-1 

0.3 

0.2 

0.2 

0.1 

0.1 

SKE4-N04 

0.2 

0.2 

0.1 

0.1 

SKE4-N06 

0.2 

0.2 

0.1 

0.1 

SKE4-N10 

SDU4-2 

0.4 

0.2 

0.2 

SKE4-N14 

0.4 

0.2 

0.2 

SKE4-N16 

SDU4-3 

0.4 

0.2 

SKE4-N20 

0.2 

0.2 

SKE4-N30 

0.2 

0.2 

 

 

 

Summary of Contents for SKE4-N Series

Page 1: ...SKE4 N Remote SDU Guide 190201 SKE4 N Steam Humidifier Remote SDU Installation Guide...

Page 2: ...Electrical Supply Bottom View Illustration 1 Remote SDU Table 1 Dimensions and Weight Model SDU Dimensions inch mm Steam Outlet Weight lb kg A B Qty Diameter inch mm SKE4 N02 SKE4 N04 SKE4 N06 SDU4 1...

Page 3: ...ount the SDU to the wall on brackets supplied Do not drill mounting holes through the cabinet of the SDU Connect the steam hose to the bottom inlet of the SDU and to the humidifier steam outlet locate...

Page 4: ...knockout hole remove the plug from the open silicone pipe near the water fill valve Then insert a fitting not supplied inside of the silicone pipe and connect the end of the condensate hose not suppli...

Page 5: ...D E Illustration 3 Remote SDU Mounting Bracket Table 2 Remote SDU Mounting Bracket Dimensions Model SDU Dimensions inch mm A B C D E SKE4 N02 SKE4 N04 SKE4 N06 SDU4 1 16 406 6 171 13 7 348 19 1 29 SK...

Page 6: ...l remote SDU cover 1 Secure the two side covers onto the remote SDU mounting bracket by fastening them with 3x 6 32 M3 5 x 0 6 nuts supplied 2 Secure the front cover onto the remote SDU mounting brack...

Page 7: ...stall a circuit breaker To provide strain relief to the supply cable install a knock out not supplied at the bottom of the SDU Ensure that the size of the wire conductors is appropriate for the curren...

Page 8: ...Ground L N Wiring by others SDU Terminal Block Humidifier Terminal Block Illustration 5 Wiring for SDU4 1 Model at 120V or 240V 1ph SDU Fan Fuse PD Switch Red Black White Red Grey Transformer Red Gree...